The circle indicates the location of the compressed air and electrical connections.
NOTE:
Remember that you are required to follow the local laws, regulations, and standards that apply to the
electrical installation of your processing station.
NOTE:
The processing station is not supplied with any power cable.
Power distribution unit (PDU)
The PDU must be rated to meet the power requirements of the processing station, and should be in accordance
with the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
Circuit breakers (required)
The circuit breakers must meet the requirements of the processing station and should be in accordance with the
Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
The processing station requires one or two branch circuit breakers, depending on the installation.
The processing station has built-in Residual-Current Circuit Breakers (RCCB), also known as Ground Fault Circuit
Interrupters (GFCI), with 30 mA sensitivity. If local laws require an external RCCB or GFCI for earth fault
protection, install a device with sensitivity of 100 mA or higher, with appropriate rated current for the supply
configuration, and ensure that other protective devices for earth fault protection upstream from the one
supplying the processing station are always greater than the one selected for the processing station.
WARNING!
Ensure that mains fault current is adequate for proper operation of the supplementary circuit
breakers incorporated in the equipment (5 kA rated interrupting capacity).
WARNING!
Ensure that the processing station's built-in Residual-Current Circuit Breakers (RCCB) or Ground
Fault Circuit Interrupters (GFCI) operate in the case of a current leakage fault to the product chassis, even when
an isolation device (such as an isolating transformer) is used to supply power to the processing station.
Power specifications
Configuration 1: 220–240 V line-to-neutral one-phase configuration
Printer specifications
Number of power lines
Input voltage (line to neutral)
Input frequency
Power consumption (typical)
Maximum load current (per phase)
Branch circuit breaker specifications
Power cable specifications
Configuration
ENWW
1 line + N + PE
220–240V (±10%)
50 Hz
2.6 kW
14 A
2 poles, 20 A, type J
2 lines + PE
Processing station electrical configuration
31