HP Jet Fusion 4200 Product Documentation Site Preparation Manual page 22

Table of Contents

Advertisement

NOTE:
The printer is not supplied with any power cable.
Power distribution unit (PDU)
The PDU must be rated to meet the power requirements of the printer, and should be in accordance with the
Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
Circuit breaker (required)
The printer requires a circuit breaker, which must meet the requirements of the printer and should be in
accordance with the Electrical Code requirements of the local jurisdiction of the country where the equipment is
installed.
The printer has built-in Residual-Current Circuit Breakers (RCCB), also known as Ground Fault Circuit Interrupters
(GFCI), with 30 mA sensitivity. If local laws require an external RCCB or GFCI for earth fault protection, install a
device with sensitivity of 100 mA or higher, with appropriate rated current for the supply configuration, and
ensure that other protective devices for earth fault protection upstream from the one supplying the printer are
always greater than the one selected for the printer.
WARNING!
breakers incorporated in the equipment (6 kA rated interrupting capacity).
WARNING!
Interrupters (GFCI) operate in the case of a current leakage fault to the product chassis, even when an isolation
device (such as an isolating transformer) is used to supply power to the printer.
Power specifications
The printer supports two different electrical configurations. Select the right configuration based on the three-
phase line-to-line voltage supplied by the PDU. Refer to the appropriate table of specifications according to the
selected configuration.
In the case of the 200–240 V line-to-line three-phase configuration, take into account that the input voltage may
vary between −10% and +10%. That means that the minimum voltage accepted by the printer is 180 Vac.
If you can ensure that the power network meets the specifications constantly at all times of day, then it is not
necessary to install a UPS. However, if the voltage falls too low to provide good quality, the printer will show a
system error. Therefore, if the printer is showing errors related to mains power, you must install a UPS to get the
minimum required input voltage.
Configuration 1: 380–415 V line-to-line three-phase configuration
Printer specifications
Number of power lines
Input voltage (line to line)
Input voltage (line to neutral)
Input frequency
Power consumption (typical)
Maximum load current (per phase)
18
Chapter 2 Site preparation requirements for the printer
Ensure that mains fault current is adequate for proper operation of the supplementary circuit
Ensure that the printer's built-in Residual-Current Circuit Breakers (RCCB) or Ground Fault Circuit
3 lines + N + PE
380–415 V~ (±10%)
220–240 V~ (±10%)
50/60 Hz
9–11 kW
30 A (up to 35 A repetitive peak current)
ENWW