Configurations Continued
Battery Options
The charger can be set to charge four different types of batteries: wet lead-acid, AGM, gel, or LFP. The charger is
set to AGM by default by the factory. The battery type may be changed at the factory or through the NVM Setup
Utility. To determine what type of battery the inverter is configured for, monitor the LED blink code at startup and
reference the LED status chart.
Low Battery Shutdown
Low battery shutdown is a protective measure to prevent deep discharge of the battery and/or to make sure that
the starting batteries have enough power to start the vehicle.
NOTE: The inverter may be de-rated when the input voltage approaches the low battery set-point. To conserve
battery voltage, the internal inverter fan may turn off. This will cause the inverter to go into high temp shutdown if
the load is large enough.
Branch Circuit Rating
The branch circuit rating (BCR) can be set to 0, 5, 10, 15, 20, 25, or 30 A. If set to 0 A, the charger will not enable,
but bypass power will still be available. The default factory setting is 15 A. The BCR may be changed at the factory
or through the NVM Setup Utility, 7 Seg Display, or option LCD remote.
Change the BCR on the 7-Seg Display
1. Press "Menu" once.
2. Press "Select" to cycle through available options.
3. Press "Menu" to exit.
AC Line Qualify Time
The AC line qualification time is the setting that adjusts the time that it takes for the charger and bypass to start
once qualified AC power has been applied to the charger input. This time can be set to any value between 5 and 30
seconds, in 5 second increments. The default setting is 30 seconds This setting may be changed at the factory or
through the NVM Setup Utility.
CAN Instance and Baud Rate
The CAN instance can be changed from 1–13. This is useful if there are multiple inverters being used on the same
CAN network. Multiple inverters should not share the same CAN instance. The baud rate may be changed between
250k and 500k. The default settings for the inverter are instance 1 and baud rate 250k. These values may be changed
at the factory or through the NVM Setup Utility.
Custom Battery Changes
The CV timout, CV VDC, float VDC, max charge ADC, and battery amp hour may be customized. For LFP
batteries, the battery high temperature shutdown, low temperature shutdown, and cold reduced shutdown points
may also be customized. These values may be changed through the NVM Setup Utility or optional LCD remote.