Case 3: Three or More Units, Side-by-Side
For all models, there must be a minimum distance between
any units placed side-by-side; however, performance may be
affected at this distance. Minimum distances are: models 030
to 070 - 4 feet, models 075 to 101 - 5 feet, models 110 to 241
- 6 feet.
Figure 9
and
Figure 10
adjustments as the distance between units increases.
NOTE: Data in
Figure 9
and
with a unit on each side. See Case 2 adjustment
factors for the two outside units.
Figure 8: Three or More Units, Side-by-Side
Figure 9: Case 3 - Full Load Capacity Reduction
Full Load Capacity Reduction
6.0
5.0
4.0
3.0
2.0
1.0
0.0
4
5
Distance Between Units
AGZ030-035E
AGZ0110-130E
AGZ226-241E
Figure 10: Case 3 - Power Increase
Power Increase
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
0.0
4
5
Distance Between Units (ft)
AGZ030-035E
AGZ0110-130E
AGZ226-241E
www.DaikinApplied.com
depict Case 3 performance
Figure 10
is for the middle unit
6
AGZ040-070E
AGZ075-101E
AGZ140-180E
AGZ191-211E
6
AGZ040-070E
AGZ075-101E
AGZ140-180E
AGZ191-211E
Installation and Application Information
Case 4: Open Screening Walls
Decorative screening walls are often used to help conceal a
unit either on grade or on a rooftop. When possible, design
these walls such that the combination of their open area
and distance from the unit (see
performance adjustment. If the wall opening percentage is less
than recommended for the distance to the unit, it should be
considered as a solid wall. It is assumed that the wall height is
equal to or less than the unit height when mounted on its base
support. If the wall height is greater than the unit height, see
Case 5: Pit Installation for performance adjustment factors.
The distance from the sides of the unit to the side walls must
be sufficient for service, such as opening control panel doors.
For uneven wall spacing, the distance from the unit to each
wall can be averaged providing no distance is less than 4 feet.
Values are based on walls on all four sides.
Figure 11: Case 4 - Allowable Wall Open Area
9.0
8.0
7.0
6.0
5.0
4.0
3.0
0
10
8
8
9
IOM 1206-13 • TRAILBLAZER
Figure
11) do not require
Wall Free Area vs. Distance
20
30
40
% Open Wall Area
AGZ030-070E
AGZ075-101E
AGZ110-130E
AGZ140-180E
AGZ191-241E
MODEL AGZ CHILLERS
®