EXV Module 1 and 2
These modules will be used only when the expansion valve type is electronic.
Table 30: Digital Inputs
Description
DI1
Circuit 1 or 2 MLP Switch
Heat Recovery Request
X2
Switch
Table 31: Digital Outputs
Description
Circuit 1 or 2 Fan
DO1
Output 5
Table 32: Analog Outputs
Description
Heat Recovery Pump/
X1
Valve
Heat Recovery Pump/
X3
Valve
Table 33: Stepper Motor Output
Description
M1+, M1-
EXV Stepper Coil 1
M2+, M2-
EXV Stepper Coil 2
Condenser Fan Output Labels
All condenser fan output labels, both the digital outputs and analog speed signals, will be labeled according to which fans are
connected to each one. The following tables show the fans connected to each output for each configuration.
Table 34: AGZ-E Models without VFDs
Physical
Output Descr .
Speed 1
Speed 2
Fan Output 1
UC DO3
Fan Output 2
UC DO4
Fan Output 3
UC DO5
Fan Output 4
UC DO6
Fan Output 5
EEXV1 DO1
Speed 1
Speed 2
Fan Output 1
UC DO7
Fan Output 2
UC DO8
Fan Output 3
UC DO9
Fan Output 4
UC DO10
Fan Output 5
EEXV2 DO1
IOM 1206-13 • TRAILBLAZER
Output Off
Output On
Fault
No Fault
No Request
Request
Output Off
Output On
Fan(s) Off
Fan(s) On
Output Signal
0-10VDC
4-20 mA
Current
Output
4
UC X5
UC X2
Fan 11
Fan 11
Fan 12
Fan 12
Fan 13
UC X6
UC X3
Fan 21
Fan 21
Fan 22
Fan 22
Fan 23
MODEL AGZ CHILLERS
®
Number of Fans
6
8
10
Fan 11
Fan 11
Fan 12
Fan 12
Fan 13
Fan 13
Fan 14
Fan 14
Fan 15
Fan 21
Fan 21
Fan 22
Fan 22
Fan 23
Fan 23
Fan 24
Fan 24
Fan 25
54
Unit Controller Operation
12
14
Fan 11
Fan 11/13
Fan 12
Fan 12
Fan 13
Fan 14/16
Fan 14/16
Fan 15
Fan 15
Fan 17
Fan 21
Fan 21/23
Fan 22
Fan 22
Fan 23
Fan 24/26
Fan 24/26
Fan 25
Fan 25
Fan 27
www.DaikinApplied.com