Refrigerant Charge - Daikin Trailblazer AGZ030-101E Installation, Operation And Maintenance Manual

Air-cooled scroll compressor chillers with high efficiency variable speed fan technology
Table of Contents

Advertisement

Table 4: Refrigerant Charge - Microchannel Units
Unit
Models
Replaceable Core Filter Drier
Circuit 1
030E
17 (7.7)
035E
16 (7.3)
040E
23 (10.5)
045E
23 (10.5)
050E
23 (10.5)
055E
23 (10.5)
060E
23 (10.5)
065E
23 (10.5)
070E
23 (10.5)
075E
46 (20.9)
076E
43 (19.6)
080E
46 (20.9)
081E
43 (19.6)
090E
48 (21.8)
091E
45 (20.5)
100E
48 (21.8)
101E
45 (20.5)
110E
64 (29.1)
120E
65 (29.5)
130E
65 (29.5)
140E
76 (34.5)
150E
76 (34.5)
161E
78 (35.4)
170E
80 (36.3)
180E
80 (36.3)
87 (39.5)
191E
91 (41.3)
211E
226E
107 (48.6)
241E
111 (50.4)
IOM 1206-13 • TRAILBLAZER
Microchannel Coil Unit Operating Charge - lbs (kg)
Packaged Units
Sealed Filter Drier
Circuit 2
Circuit 1
17 (7.7)
15 (16.8)
16 (7.3)
14 (6.4)
23 (10.5)
21 (9.5)
23 (10.5)
21 (9.5)
23 (10.5)
21 (9.5)
23 (10.5)
21 (9.5)
23 (10.5)
21 (9.5)
23 (10.5)
21 (9.5)
23 (10.5)
21 (9.5)
46 (20.9)
43 (19.6)
46 (20.9)
43 (19.6)
48 (21.8)
45 (20.5)
50 (22.7)
47 (21.4)
64 (29.1)
65 (29.5)
65 (29.5)
76 (34.5)
76 (34.5)
78 (35.4)
80 (36.3)
80 (36.3)
87 (39.5)
91 (41.3)
107 (48.6)
111 (50.4)
MODEL AGZ CHILLERS
®
Heat Recovery Units
Replaceable Core Filter Drier
Circuit 2
Circuit 1
15 (16.8)
14 (6.4)
21 (9.5)
21 (9.5)
21 (9.5)
21 (9.5)
21 (9.5)
21 (9.5)
21 (9.5)
49 (22)
46 (20.9)
49 (22)
46 (20.9)
51 (23)
48 (21.8)
52 (24)
48 (21.8)
69 (31)
69 (31)
69 (31)
82 (37)
82 (37)
84 (38)
86 (39)
86 (39)
95 (43)
99 (45)
119 (55)
121(55)
38

Refrigerant Charge

Refrigerant Charge
Circuit 2
49 (22)
46 (20.9)
49 (22)
46 (20.9)
51 (23)
48 (21.8)
52 (24)
50 (22.7)
69 (31)
69 (31)
69 (31)
82 (37)
82 (37)
84 (38)
86 (39)
86 (39)
95 (43)
99 (45
119 (55)
121(55)
www.DaikinApplied.com