Table 41: Evaporator Water Freeze
Evaporator Glycol
Range
No
2.2 to 5.6°C (36 to 42.1°F)
Yes
-28.89 to 5.6°C (-20 to 42.1°F)
Table 42: Low Ambient Lockout
Fan VFD Configuration
None
1/cir or 2/cir
Table 43: Low Evaporator Pressure
Available Mode Selection
Hold - Without Glycol
Hold - With Glycol
Unhold - Without Glycol
Unhold - With Glycol
Table 44: Design Conditions
Description
Design Evaporator EWT
Design Evaporator LWT
Design Evaporator Water Flow
Design mes Circuit 1/2
Design Ambient Temperature
Design Condenser Approach Circuit 1/2
Design Full Load Efficiency
Design IPLV
Design Rated Capacity
Table 45: Administration and Service Support
Description
Unit G.O. Number
Unit Serial Number
Next Maintenance Month
Next Maintenance Year
Service Support Reference
Controller Time
Controller Date
UTC Difference
Daylight Savings Time Enable
Daylight Savings Time Start Month
Daylight Savings Time Start Week
Daylight Savings Time End Month
Daylight Savings Time End Week
Operator Password Disable
Apply Changes
Active Alarm Clear
Alarm Log Clear
Power Restore Event Log - Day Selection
Display Units
IOM 1206-13 • TRAILBLAZER
Range
0 to 15.6°C (32 to 60.1°F)
-23.3 to 15.6°C (-9.9 to 60.1°F)
Range
669 to 793 KPA (97 to 115 PSI)
317 to 793 KPA (46 to 115 PSI)
669 to 793 KPA (97 to 115 PSI)
317 to 793 KPA (46 to 115 PSI)
Default
0°C (32°F)
0°C (32°F)
0 lph (0 gpm)
0°C (0°F)
0°C (32°F)
0°C (0°F)
0%
0
0 tons
Default
"Enter Data"
"Enter Data"
January
2009
999-999-9999
From Controller Timeclock
From Controller Timeclock
-60 minutes
Yes
March
2nd Week
November
1st Week
Off
No
Off
No
Current
English
MODEL AGZ CHILLERS
®
Unit Controller Operation
Range
-9.5°C to 28.34°C (14.9°F to 83°F)
-9.5°C to 18.34°C (14.9°F to 65°F)
0 to 908399 lph (0 to 4000 gpm)
0°C to 10°C (0°F to 18°F)
-28.89°C to 51.67°C (-20°F to 125°F)
0°C to 40°C (0°F to 72°F)
0 to 100%
0 to 100
0 to 1000 tons
Range
Alphanumeric string of up to 16 characters
Alphanumeric string of up to 20 characters
January through December
2009 - 2100
Any 10 digit phone number
00:00:00 to 23:59:59
1/1/2000 to 12/31/2050
-3276 to 32767 minutes
No, Yes
January through December
1st through 5th Week
January through December
1st through 5th Week
Off, On
No, Yes
Off, On
No, Yes
Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
English, Metric