Seasonal Wind And Cautions In Winter - LG THERMA V Installation Manual

Air-to-water heat pump
Hide thumbs Also See for THERMA V:
Table of Contents

Advertisement

INSTALLATION OF OUTDOOR UNIT
60

Seasonal wind and cautions in winter

• Sufficient measures are required in a snow area or severe cold area in winter so that product
can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes
on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the
hood to the system.
• Install the outdoor unit at the higher installation console by 500 mm than the average snowfall
(annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 100 mm, always
remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not exceed
the width of the product. (If width of the frame is wider than that of the product, snow may
accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.