3Way Valve(A) - LG THERMA V Installation Manual

Air-to-water heat pump
Hide thumbs Also See for THERMA V:
Table of Contents

Advertisement

ACCESSORIES INSTALLATION
130

3Way Valve(A)

3Way Valve(A) is required to operate DHW water tank. Role of 3way valve is flow switching
between under floor heating loop and water tank heating loop.
Plus, it is required to operate 3
General Information
supports following 3way valve.
Type
Power
SPDT
3-wire
220-240 V~
(1)
(1) : SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow A), Live 2
(for selecting Flow B), and Neutral (for common).
(2) : Flow A means 'water flow from the unit to under floor water circuit.'
(3) : Flow B means 'water flow from the unit to DHW water tank.'
How to wire 3way valve(A)
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the unit.
Step 2. Find terminal block and connect wire as below.
3WAY VALVE
(A)
8
9
10
L
L1
N
BR
BK
BL
(W)
(U)
(N)
3way valve
(W) : Live signal (Water tank heating) from PCB to 3way valve
(U) : Live signal (Under floor heating) from PCB to 3way valve
(N) : Neutral signal from PCB to 3way valve
rd
party boiler.
Operating Mode
Selecting "Flow A" between
"Flow A" and "Flow B" (2)
Selecting "Flow B" between
"Flow A" and "Flow B" (3)
WARNING
!
• 3way valve should select water tank loop when electric
power is supplied to wire (W) and wire (N).
• 3way valve should select under floor loop when electric
power is supplied to wire (U) and wire (N).
Supported