Water Flow Control

This function controls the water flow by controlling the water pump. Select the way to control
the water pump and set the target value
• In the installer setting list, select Configuration category, and press [OK] button to move to the
detail screen.
• Optimal Flow Rate
The water pump is automatically controlled at the optimum flow rate required according to the
desired temperature of the Main screen.
• Pump Capacity
It operates with the capacity set for the water pump.
• Fixed Flow Rate
The water pump is automatically controlled to maintain the set flow rate.
• Fixed ΔT
Set the target ΔT (*ΔT = temperature difference between inlet and outlet water temperature)
The water pump is automatically controlled to maintain the set ΔT.
Optimal Flow Rate
(Default)
OK
Flow Control Method
Pump Capacity
Fixed Flow Rate
INSTALLER SETTING
Fixed ΔT