Screed drying

This function is a unique feature of AWHP that, when AWHP is installed in a new concrete
structure, controls the specific temperature floor heating out temperature for a certain period of
time to cure the floor cement.
• In the installer setting list, select Screed drying category, and press [OK] button to move to the
detail screen.
How to display
Main Screen - Displays 'Screed drying' on the desired temperature display. The step in progress
at the bottom of the display is displayed.
Setting value
- Start-up step: 1 ~ 11
- Maximum temperature : 35 °C ~ 55 °C
- Step 8 Holding time : 1 days ~ 30 days
Function operation
- It is performed by the following procedure from the selected starting step.
- After all steps are completed, turn off the cement curing operation.
Step
1
Leaving Water
target
25
temperature[°C]
Duration
72
[hours]
※ If the upper limit setting value of the heating LW temperature is 55 °C or lower, it is set to
55 °C forcibly.
If the lower limit setting value of the heating LW temperature is 25 °C or higher, it is set to
25 °C forcibly.
OK
2
3
4
Max.T
Off
25
96
72
24
INSTALLER SETTING
5
6
7
35
45
Max.T Max.T
Holding
24
24
24
time
8
9
10
11
45
35
25
72
72
72