Water Pump Capacity; Pressure Drop - LG THERMA V Installation Manual

Air-to-water heat pump
Hide thumbs Also See for THERMA V:
Table of Contents

Advertisement

Water pump Capacity

The water pump us variable type which is capable to change flow rate, so it may be required to
change default water pump capacity in case of noise by water flow. In most case, however, it is
strongly recommended to set capacity as Maximum.
NOTE
• To secure enough water flow rate, do not set water pump capacity as Minimum.
It can lead unexpected flow rate error CH14.

Pressure Drop

NOTE
When installing the product, install additional pump in consideration of the pressure loss and
pump performance.
If flow-rate is low, overloading of product can occur.
Capacity
Rated flow-rate
[kW]
[LPM]
16
14
12
9
7
5
Capacity
Rated flow-rate
[kW]
[LPM]
9
7
5
Capacity
Rated flow-rate
[kW]
[LPM]
16
14
40.25
12
Pump Head [m]
(at rated flow-rate)
46.0
9.5
40.0
10.0
34.0
10.7
26.0
11.3
20.0
11.6
17.0
11.8
Pump Head [m]
(at rated flow-rate)
25.9
6.1
20.1
7.3
14.4
7.5
Pump Head [m]
(at rated flow-rate)
46
9
9.3
34.5
9.8
PIPING AND WIRING FOR INDOOR UNIT
Product pressure
drop [m]
(Plate heat exchanger)
1.4
1.1
0.8
0.4
0.3
0.2
Product pressure
drop [m]
(Plate heat exchanger)
0.4
0.3
0.2
Product pressure
drop [m]
(Plate heat exchanger)
1.4
1.1
0.8
91
(For R410A)
Serviceable
Head [m]
8.1
8.9
9.9
10.9
11.3
11.6
(For R32)
Serviceable
Head [m]
5.7
7.0
7.3
(For Hydrosplit)
Serviceable
Head [m]
7.6
8.2
9

Advertisement

Table of Contents
loading

Table of Contents