Table of Contents

Advertisement

3. Installation Space
3.2 Collective / continuous installation
Space required for collective installation and continuous installation: When installing several units, leave space
between each block as shown below considering passage for air and people.
1. One row of stand alone installation
2. Rows of collective installation (2 or more)
• L should be smaller than H
L ≤ H

Seasonal wind and cautions in winter

• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole, the
system may malfunction. If it is installed at snowy area, attach the hood to the system.
• The raised support platform must be high enough to allow the unit to remain above possible snow drifts, and must be high-
er than the maximum anticipated snowfall for the location.
Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
6 _