Customer Supplied Thermostat; Optional Factory Supplied Thermostat - Daikin Maverick I Installation And Maintenance Manual

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Customer Supplied Thermostat

The customer supplied room thermostat must be compatible
with the spark ignition control on the unit. Generally, all
thermostats that are not of the "current robbing" type are
compatible with the integrated furnace control. The low voltage
wiring should be sized as shown in
Install the room thermostat in accordance with the instruction
sheet packed in the box with the thermostat.
Figure 17 on page 17
for an example of a typical customer
supplied wiring diagram.
Table 6: Field Wire Size for 24 Volt Thermostat
3.0
16
Thermostat
2.5
16
Load Amps
2.0
18
50
NOTE: (1) The total wire length is the distance from the furnace to the
thermostat and back to the furnace. DO NOT USE CONTROL WIRING
SMALLER THAN NO. 18 AWG.
IM 972-2 • MAVERICK I ROOFTOP SYSTEMS
Table
6.
Solid Copper Wire, AWG
14
12
10
10
14
12
12
10
16
14
12
12
Length of Run – Feet (1)
100
150
200
250
300

Optional Factory Supplied Thermostat

The optional factory supplied T-170 commercial setback digital
thermostat
(Figure
provide precise time and temperature control. This thermostat
offers the flexibility to design heating and cooling programs that
fit building needs (refer to
factory supplied thermostat wiring diagram.
Figure 16: Optional T-170 Thermostat
10
10
10
Table 7: Optional Factory Supplied Thermostat
Specifications
Electrical Rating Single Stage:
Electrical Rating Staging:
Terminal Load:
Setpoint Range:
Anticipation, Heating:
Anticipation, Cooling:
Rated Differential Single Stage: Heat 0.5° to .5°F, Cool 0.8° to 2.2°F
Rated Differential Staging:
Operating Ambient:
Shipping Temperature Range:
Dimensions (H × W × D):
16
Electrical Installation
16) uses microcomputer technology to
Table
7).
Figure 18
for an optional
mV to 30 V (ac), NEC Class II, 50/60 Hz
or DC
20 to 30 V (ac), NEC Class II
5 A per terminal, 2.5 A max. combined
45° to 99°F (7° to 37°C)
Adjustable
Adjustable
Heat 0.5° to .5°F, Cool 0.5° to 2.2°F
32° to +0°F (0° to +43°C) Operating
Humidity 90% non-condensing max.
-4° to 50°F (-20° to 65°C)
4-1/8" × 6-7/8" × 1-3/8"
www.DaikinApplied.com