Daikin Maverick I Installation And Maintenance Manual page 45

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Figure 38: System Charging Chart: MPS 020B
www.DaikinApplied.com
SYSTEM CHARGE CHART - REFRIGERANT 410A
20 TON, CIRCUITS 1 & 2
CAUTION:
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING
REFRIGERANT CHARGE.
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS
BEFORE FINAL REFRIGERANT CHECK!
MEASURE PRESSURE AT COMPRESSOR SUCTION AND DISCHARGE.
INSTRUCTIONS:
MEASURE OUTDOOR AMBIENT TO UNIT.
PLACE (X) ON CHART WHERE SUCTION AND DISCHARGE INTERSECT.
IF (X) IS BELOW OUTDOOR AMBIENT LINE, ADD CHARGE AND REPEAT
STEPS 1-3.
IF (X) IS ABOVE OUTDOOR AMBIENT LINE, RECOVER EXCESS CHARGE
AND REPEAT STEPS 1-3.
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
100
105
110
115
120
SUCTION PRESSURE (PSIG)
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
100
105
110
115
120
SUCTION PRESSURE (PSIG)
20 TON, CIRCUIT 2
125
130
135
140
145
150
155
20 TON, CIRCUIT 1
125
130
135
140
145
150
155
45
115
105
95
85
75
65
55
160
165
115
105
95
85
75
65
55
160
165
IM 972-2 • MAVERICK I ROOFTOP SYSTEMS
Maintenance