Performance Data - Daikin Maverick I Installation And Maintenance Manual

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Figure 27: Airflow Performance—MPS 015B
Airflow
CFM [L/s]
0 .1 [ .02]
0 .2 [ .05]
0 .3 [ .07]
0 .4 [ .10]
RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W
4800
[2265]
5000
[2359]
5200
[2454]
5400
[2548]
5600
[2643]
5800
576 1588 601 1715 625 1840 649 1964 672 2085 694 2204 716 2321 737 2436 757 2548 778 2614 798 2735 817 2858 836 2985 855 3116 873 3249 891 3386 909 3527
[2737]
6000
585 1683 610 1813 634 1940 657 2065 680 2187 702 2308 724 2426 744 2543 765 2657 785 2731 805 2856 824 2984 843 3116 861 3251 879 3389 897 3531 914 3676
[2831]
6200
570 1650 595 1783 619 1913 643 2042 666 2169 688 2293 710 2415 731 2535 752 2653 773 2728 792 2854 812 2984 831 3116 850 3253 868 3392 886 3535 903 3682 920 3832
[2926]
6400
579 1750 604 1885 628 2017 652 2148 674 2276 697 2402 718 2526 739 2648 760 2767 780 2852 800 2983 819 3118 838 3255 856 3396 875 3541 892 3688 909 3839 926 3994
[3020]
6600
589 1854 614 1991 637 2125 661 2257 683 2386 705 2514 727 2640 748 2763 768 2884 788 2984 808 3119 827 3258 845 3400 863 3546 881 3695 899 3847 916 4003 —
[3114 ]
6800
574 1822 599 1961 623 2099 647 2235 670 2369 692 2500 714 2629 735 2756 756 2882 776 2984 796 3121 815 3262 834 3405 853 3552 871 3702 888 3856 905 4013 922 4173 —
[3209 ]
7000
584 1930 609 2072 633 2211 656 2349 679 2484 701 2617 723 2748 744 2877 764 3003 785 3124 804 3265 823 3410 842 3559 860 3710 878 3865 895 4024 912 4185 929 4350 —
[3303]
7200
570 1897 595 2042 619 2185 643 2327 666 2466 689 2602 711 2737 732 2870 753 3000 773 3127 793 3270 812 3416 831 3566 849 3719 868 3875 885 4035 902 4198 919 4364 —
[3398]
NOTE: L-Drive left of bold line, M-Drive right of bold line.
Drive Package
Motor H .P . [W]
Blower Sheave
Motor Sheave
Turns Open
1
RPM
733
NOTES:
1. Factory sheave settings are shown in bold type.
2. Do not set motor sheave below minimum turns open shown.
3. Readjustment of sheave required to achieve rated airflow at AHRI minimum external static pressure.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance (below) to duct resistance to determine total external static pressure.
Component Airflow Resistance 15 Ton [52.7kW]
CFM [L/s]
WetCoil
Downflow
Downflow Economizer RA Damper Open
Horizontal Economizer RA Damper Open
Airflow Correction Factors 15 Ton [52.7kW]
4800
5000
CFM [L/s]
[2265]
[2359]
Total MBH
0.97
0.97
Sensible MBH
0.87
0.90
Power kW
0.98
0.98
NOTE: Multiply correction factor times gross performance data resulting sensible capacity cannot exceed total capacity.
[ ] Designates Metric Conversions
IM 972-2 • MAVERICK I ROOFTOP SYSTEMS
External Static Pressure — Inches of Water [kPa]
0 .5 [ .12]
0 .6 [ .15]
0 .7 [ .17]
0 .8 [ .20]
583 1393 608 1508 632 1621 656 1732 679 1841 701 1947 723 2052 744 2154 764 2254 785 2326 805 2430 825 2537 844 2647 863 2761 881 2878
591 1476 616 1593 640 1707 663 1820 686 1930 708 2038 729 2145 750 2248 771 2350 791 2420 811 2528 830 2640 850 2755 868 2873 887 2995
575 1442 600 1562 624 1681 648 1797 671 1911 693 2023 715 2133 736 2241 757 2346 777 2410 797 2520 817 2633 836 2749 855 2869 874 2992 892 3118
583 1530 608 1652 632 1772 655 1890 678 2005 701 2119 722 2231 743 2340 764 2447 784 2512 804 2626 823 2744 842 2865 861 2989 879 3117 897 3248
592 1621 616 1745 640 1866 663 1986 686 2103 708 2218 729 2331 750 2442 770 2551 791 2620 810 2739 830 2861 849 2987 867 3116 885 3248 903 3384
L
3 [2237.1]
BK105H
1VL-44
2
3
4
701
669
640
4800
5000
[2265]
[2359]
0.03
0.04
[.01]
[.01]
0.05
0.05
[.01]
[.01]
0.09
0.10
[.02]
[.02]
0.00
0.01
[.00]
[.00]
5200
5400
5600
[2454]
[2548]
[2643]
0.98
0.98
0.99
0.92
0.94
0.97
0.99
0.99
0.99
Model MPS 015
Voltage 208/230, 460, 575 — 3 Phase
0 .9 [ .22]
1 .0 [ .25]
1 .1 [ .27]
1 .2 [ .30]
1 .3 [ .32]
5
6
1
605
572
927
5200
5400
5600
5800
[2454]
[2548]
[2643]
[2737]
Resistance Inches of Water [kPa]
0.05
0.06
0.06
0.07
[.01]
[.01 ]
[.01]
[.02 ]
0.05
0.05
0.05
0.05
[.01]
[.01 ]
[.01]
[.01 ]
0.10
0.11
0.12
0.13
[.02]
[.03 ]
[.03]
[.03 ]
0.01
0.02
0.02
0.03
[.00]
[.00 ]
[.00]
[.01]
5800
6000
6200
[2737]
[2831]
[2926]
1.00
1.00
1.01
0.99
1.02
1.04
1.00
1.00
1.00
30

Performance Data

1 .4 [ .35]
1 .5 [ .37]
1 .6 [ .40]
1 .7 [ .42]
M
5 [3728.5]
BK105 H
1VP-56
2
3
4
903
873
840
6000
6200
6400
6600
[2831]
[2926]
[3020]
[3114]
[3209]
0.08
0.09
0.10
0.10
[.02]
[.02]
[.02 ]
[.02]
0.05
0.06
0.06
0.06
[.01]
[.01]
[.01]
[.01]
0.13
0.14
0.15
0.16
[.03]
[.03]
[.04 ]
[.04]
0.03
0.04
0.04
0.05
[.01]
[.01]
[.01 ]
[.01]
6400
6600
6800
[3020]
[3114]
[3209]
1.02
1.02
1.03
1.06
1.09
1.11
1.01
1.01
1.01
www.DaikinApplied.com
Performance Data
1 .8 [ .45]
1 .9 [ .47]
2 .0 [ .50]
5
6
808
775
6800
7000
7200
[3303]
[3398]
0.11
0.12
0.13
[.03]
[.03 ]
[.03]
0.07
0.08
0.08
[.02 ]
[.02]
[.02]
0.16
0.17
0.18
[.04]
[.04 ]
[.04]
0.05
0.06
0.06
[.01]
[.01 ]
[.01]
7000
7200
[3303]
[3398]
1.03
1.04
1.14
1.16
1.02
1.02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mps015bMps025bMps020b