Module; Programming/View Digitrip 1150; Main Menu; Power Up Sequence - Eaton Cutler-Hammer Digitrip 1150 Instructions Manual

Hide thumbs Also See for Cutler-Hammer Digitrip 1150:
Table of Contents

Advertisement

I.L. 70C1036H01
3.5 PT Module
The PT Module is internally wired in the breaker to the
line side breaker terminals. It provides signal data to
calculate voltage, power, energy and related data. The PT
module is is a three phase, three wire input and three
wire output step down transformer with a wye to wye
hookup.
WARNING
A DIELECTRIC DISCONNECT PLUG LOCATED ON
THE LEFT SIDE OF THE BREAKER IS PROVIDED
WITH THIS MODULE AND IS TO BE REMOVED WHEN
DIELECTRIC TESTING OF THE BREAKER IS CON-
DUCTED.
Disconnect Plug
Figure 2.10 PT Module with Dielectric Disconnect Plug
Effective 8/18/99
Courtesy of NationalSwitchgear.com
PT Module
4.0 PROGRAMMING/VIEWING DIGITRIP 1150 via FRONT PANEL

4.1 Main Menu

4.1.0 Power Up Sequence

When the Digitrip 1150/1150i unit is first powered-up, two
different display messages are possible. If the Digitrip
has been previously commissioned with customer made
settings, the display will alternate between "Cutler-
Hammer DT 1150" and "Customer Settings in Use"
messages. Following this the display will enter into the
main menu. See Appendix D-1.
If Digitrip settings have not been saved previously the trip
unit is using the factory default values. On power up, the
Digitrip will then display"CHANGE FACTORY SETUP?".
This message will stay on the screen until the user
presses ESCape or the SELect pushbutton or if an alarm
or trip condition is detected.
The ESCape pushbutton action will keep the factory
settings and then will enter the main menu. The factory
setting are listed in Appendix D-23 and are not valid for
most applications. The appropriate settings need to be
defined by a qualified application engineer to provide best
overall protection and coordination for the power system.
A SELect pushbutton action will provide direct entry into
PROGRAM SETTING menu. The first item presented is
the Current CURVE type. LSIG or IEEE or (IEC) current
curve types are possible selections depending on trip unit
style. Pressing SELect again will select the curve pre-
sented in the window center and then step into the
individual elements that need programmed. The VIEW up
and down arrow selects the function while the EDIT up
and down arrow changes value. After they are set they
need to be saved by depressing the SAVE pushbutton.
The saving will place the customer settings in use. Verify
the new settings. See Appendix D-13 for program curve
and D-19 for saving and D-5 for view setting menu.

4.1.1 Pushbutton Definition

View Functions
The "View Functions" group of pushbuttons is located in
the lower right hand side of the unit and includes the View
Up (up arrow), View Down (down arrow), ESCape,
SELect, and Reset buttons.
View Up / View Down - View Up and View Down allow the
user to scroll through any available menu or submenu in
the Digitrip 1150 display.
Page 17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cutler-hammer digitrip 1150i

Table of Contents