Eaton Cutler-Hammer Digitrip 1150 Instructions Manual page 54

Hide thumbs Also See for Cutler-Hammer Digitrip 1150:
Table of Contents

Advertisement

Page 54
(Continued from D-12)
0.40 - 1.00
(steps of 0.05)
If LONG SLOPE =
I4T:
I2T:
1.0 - 5.0
2.0 - 24.0
(steps of 0.5)
(steps of 0.5)
1.5 - 10
(steps of 0.5)
(and setting
0.10 - 0.50
(steps of 0.05)
= 14x or
M 1
2.0 - M1
= 12x or
O F F
= 10x
(steps of 0.5)
Courtesy of NationalSwitchgear.com
Save
(Page D-19)
LONG
2
SLOPE
4
I T
V I E W
LONG PU
.
Ir=XXXXA
LongTIME
@ 6x Ir
.
s
LONG
O N
MEMORY
O F F
SHORT
F L A T
SLOPE
I2T
SHORT PU
.
xIr
XXXXX A
M1 xIn)
SHORT
TIME
.
s
INST PU
.
xIn
XXXXX A
PHASE
1 - 30 s
LOSS
O F F
(steps of 1 s)
AMP UN-
0 - 240 s
BALANCE
(steps of 1 s)
s
range
AMP UN-
(5% - 25% xIr)
BALANCE
O F F
XXX A
(steps of 1%)
NEUTRAL
5 0 %
PROTECT
1 0 0 %
none
none denotes defaul t
1000/1
EXT GND
800/1
CT RATIO
400/1
200/1
100/1
10/1
GROUND
TIME
0.10 - 0.50
(steps of 0.05)
.
s
GROUND
F L A T
SLOPE
I2T
GND PU
0.10 - 1.00 and OFF (IEC style only)
.
0.24 - 1.00 (IEEE) with 1200A Max
(steps of 0.01)
XXXX A
*.
"EARTH" will replace
I.L. 70C1036H01
Appendix D Page D-13
Program LSI-G
Curve
Screen is skipped if
first AMP UN-
BALANCE is set to
"OFF"
Screen is skipped if
LSIG factory style
to In value
Screens are
skipped if
LSI style
If IEC -EF style
" G R O U N D "
Effective 8/18/99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cutler-hammer digitrip 1150i

Table of Contents