Emerson Copeland EazyCool ZX Series Application Manuallines page 59

Outdoor condensing units for a2l applications
Hide thumbs Also See for Copeland EazyCool ZX Series:
Table of Contents

Advertisement

Code
Description
E41
Low-pressure switch alarm
E43
Low pressure alarm
E44
Discharge line temperature alarm
L44
Discharge line temperature lockout
E45
High condenser pressure alarm
E46
High condenser temperature alarm
E47
EXV full open in EVI
E48
Refrigerant shortage error in EVI
E49
Pumpdown alarm
E50
High side floodback alarm
E60
Max pressure alarm of superheating Not used
54
Cause
Action
Low-pressure switch
The compressor will trip
open
The pressure is below
Warning signal only
D29
Discharge line
temperature higher
The compressor will trip
than D22 for D24
seconds
Discharge line
temperature overheat
The compressor will lock out (if D26
happened D26 times
equal to 0, no compressor lockout)
within one hour
Not used
Condenser
temperature higher
The compressor is activated according
than E58 for E59
to E60
minutes
EXV full open for F40
Warning signal only
minutes
EXV full open and PHE
superheat is higher
than (F28/F29.../F37 +
F39)
Warning signal only
(F28/F29.../F37
depends on refrigerant
type)
Not used
The differential
temperature between
discharge and mid-coil
Warning signal only
is lower than H21 for
accumulated H22
minutes in H23 minutes
Reset
Automatically: low-pressure switch closed and
D28 delay time-out.
To deactivate the alarm function set parameter
D13 to "No".
Automatically: discharge line temperature lower
than D23 setting and D25 delay time-out.
Hold "start" button for 5 sec or manual power off
and on (if D26 equal to 0, compressor
automatically starts when discharge line
temperature is lower than D23 setting and D25
delay time-out).
Automatically: as soon as condenser
temperature is lower than E61.
Automatically: as soon as EXV is not at
maximum steps.
Automatically: as soon as PHE super heat is
lower than (F28/F29.../F37 + F39).
Automatically: as soon as differential
temperature between discharge and mid-coil is
higher than H21 for H24 minutes.
AGL_Unit_ZX_A2L_E_Rev00