2.11.7 Fast access menu

This menu contains the list of probes and some values that are automatically evaluated by the board
such as the superheat and the percentage of valve opening.
"nP" or "noP" stands for "Probe not present" or "Value not evaluated", "Err" means "Value out of
range" or "Probe damaged, not connected or incorrectly configured".
Entering fast access
menu
Use the
or
arrow to select
an entry, then
press
to see the value
or to go on with
another value.
Exit
Table 20: Fast access menu

2.12 Controller keyboard

2.12.1 How to lock the keyboard

Keep the
and
keys pressed simultaneously for more than 3 seconds. The "PoF" message
will be displayed and the keyboard will be locked. At this point it is only possible to see the setpoint
or the maximum or minimum temperatures stored. If a key is pressed for more than 3 seconds, the
"PoF" message will be displayed.

2.12.2 How to unlock the keyboard

Keep the
and
keys pressed simultaneously for more than 3 seconds, till the "Pon" message
is displayed.
AGL_Unit_ZX_A2L_E_Rev00
Press and release the UP arrow. The duration of the
menu in case of inactivity is 3 minutes.
The values that will be displayed depend on the
configuration of the board.
▪ P1P: Pressure value of the P1 probe (suction pressure)
▪ P2t: Temperature value of the P2 probe (not valid)
▪ P2P: Pressure value of the P2 probe (discharge pressure)
▪ P3t: Temperature value of the P3 probe (discharge line
temperature)
▪ P6t: Temperature value of the P6 probe (ambient temperature)
▪ P7t: Temperature value of the P7 probe (free)
▪ SH: Value of superheat. nA = not available
▪ oPP: Percentage of step valve opening
▪ LInJ: Status of the liquid line solenoid ("On" – "Off"). This information
is available only if one relay is set as "Liquid Line Solenoid".
▪ SEtd: Value of the dynamic setpoint (condenser fan SET). This
information is available only if the dynamic setpoint function is
enabled.
▪ AOO: Percentage of the analog output (0-10 V or TRIAC PWM
Mod.). This information is available only if the 0-10 V or TRIAC PWM
Mod. is enabled.
▪ dStO: Percentage of the PWM output driving the valve of the Digital
scroll compressor
▪ L°t: Minimum room temperature
▪ H°t: Maximum room temperature
▪ HM: Menu
▪ tU1: Voltage reading V1 (not valid in standard configuration)
▪ tU2: Voltage reading V2 (not valid in standard configuration)
▪ tU3: Voltage reading V3 (not valid in standard configuration)
▪ tA1: Current reading I1
▪ tA2: Current reading I2
Press simultaneously or wait for the timeout of about
60 seconds
21