Emerson Copeland EazyCool ZX Series Application Manuallines page 62

Outdoor condensing units for a2l applications
Hide thumbs Also See for Copeland EazyCool ZX Series:
Table of Contents

Advertisement

Pumpdown with temperature sensor in case temperature (not available on ZXDY units) – System restart is required!
Parameter
Parameter description
A19
C05
Compressor regulation probe selection
G01
Case temperature probe selection
G56
Use the liquid line solenoid
S07
C01
Compressor cut-in pressure setpoint
C02
Compressor cut-out pressure setpoint
G02
G03
Positive differential defines upper cut-in temperature
Parameter
Parameter description
A19
G12
Defrost probe selection
G23
S05
G18
Interval between defrost cycles
G19
Maximum duration of defrost
G21
Defrost termination temperature
G26
AGL_Unit_ZX_A2L_E_Rev00
Probe 7 configuration
Relay output 4
Cut-out temperature
Defrost with time intervals – System restart is required!
Probe 7 configuration
Defrost interval mode
Relay output 2
Drip time
Factory setting
nu = Not used
SuP = Suction pressure probe
nu = Not used
No
nu = Not used
4 bar rel
2 bar rel
+2 °C
1 K
Factory setting
nu = Not used
nu = Not used
nu = Not used
nu = Not used
4 min
20 min
10
1 min
Required setting
tnt = Thermostat temperature
CSt = Case temperature
tnt = Thermostat temperature
Yes
LLS = Liquid line solenoid
Adjust to application requirements
Adjust to application requirements
Adjust to application requirements
Adjust to application requirements
Required setting
EPt = Evaporator temperature
EPt = Evaporator temperature
In = By time (G18)
dEF = Defrost
Adjust to application requirements
Adjust to application requirements
Adjust to application requirements
Adjust to application requirements
57