Veris Industries FSR Series Installation Manual page 36

Ultrasonic flow meter
Table of Contents

Advertisement

TM
Rate Pulse: Open collector, 0 to 1,000 Hz maximum; 12 bit resolution,1.0 A max. Can span negative to positive rates. Square-wave or simulated turbine output.
Input/Output
(FSR1 monitors)
Alarm Outputs (2): Open collector, configure as Error alarm, Rate alarm, Signal Strength alarm, or Total/Batch pulse.
Ambient Conditions
-40 °F to 185 °F (-40 °C to 85 °C), 0 to 95 % relative humidity (non-condensing).
Type: Type 4 (IP 65).
Enclosure
Construction: Powder-coated aluminum, polycarbonate, stainless steel, polyurethane.
Size
6.0" W x 4.4" H x 3.2.2" D (152 mm W x 112 mm H x 56 mm D).
Type:
Wall: Nickel-plated steel mounting brackets.
Pipe: U bolt mounting.
Monitor Mounting
Integral Transducer: Clamped around pipe.
Conduit holes:
½" NPT Female (2).
¾" NPT Female (1).
Response Time (Flow)
0.3 to 30 seconds, user configured, for 10 % to 90 % step change in flow.
Security
Keypad lockout, user selected 4 digit password code.
Liquid Types
Most non-aerated, clean liquids.
Cable Length
Up to 990 ft (300 meters) Standard lengths 20, 50, 100 ft (6, 15, 30 meters)
FST1, FST2, FST3: (Small pipe) ½", ¾", 1", 1¼", 1½", 2" (ANSI Pipe, Copper Tube, Tube).
Pipe Sizes
FST4: 2-24 inches.
FST5: 24 inch and larger.
Environment
IP 67/NEMA 6
Pipe Surface
FST1, FST2, FST3: -40 °F to +185 °F (-40 °C to +85 °C).
Temperature
FST4, FST5: -40 °F to +250°F (-40 °C to +121 °C).
Ambient Conditions
40 °F to 185 °F (-40 °C to 85 °C), 0 to 95 % relative humidity (non-condensing)
FST1, FST2, FST3: PVC, Ultem®, and nylon cord grip, PVC cable jacket.
Housing Material
FST4, FST5: CPVC, Ultem®, and nylon cord grip, PVC cable jacket.
FST4, FST5 only: CSA Class 1, Div 1, Groups C & D; Requires intrinsically safe transducer kit with barrier.
UL 1604: Electrical Equipment for Use in Class I and II, Division 2, and Class III Hazardous (Classified) Locations.
Approvals
CSA C22.2 No. 213: Non-Incendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations.
EN 60079-0: Electrical Apparatus for Explosive Gas Atmospheres Part 0: General Requirements
EN60079-15: Electrical Apparatus for Explosive Gas Atmospheres Part 15: Electrical Apparatus with Type of Protection "n".
Utilized for configuration, calibration and troubleshooting.
USP
Compatible with Windows® 95, Windows® 98 Windows® 2000 Windows®, Windows® XP, Windows® Vista, and Windows® 7.
Direct
Alternating
Function
Current
Current
Symbol
Z205739-0D
PAGE 36
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
FSRxxxx SERIES
Electrical Symbols
Earth
Protective
(Ground)
Ground
©2013 Veris Industries
Monitor
Transducers
Software Utilities
Chassis
Ground
INSTALLATION GUIDE