Modbus Coil
Modbus
Description
Coil
Reset Totalizers
1
Table A-3.4 - Modbus Coil Map
BACnet
Object
Object Description
(Access
Point)
Signal Strength
AI1
Flow Rate (Flow model)
AI2
Energy Rate (BTU model)
Net Totalizer
AI3
Positive Totalizer
AI4
Negative Totalizer
AI5
Temperature 1
AI6
Temperature 2
AI7
Reset Totalizers
BO1
Table A-3.5 - BACnet® Object Mappings
Network Settings:
IP address, IP subnet, IP gateway, and Device Description are configured through the
web interface. IP address and subnet defaults to 192.168.0.100 and 255.255.255.0.
Connection to the web interface requires an Ethernet crossover cable, power to the
flow meter, and a PC with a web browser. Type http://192.168.0.100 in the address
bar to allow connection to the flow meter's web interface for editing.
Web Interface
user name: admin [enter]
password: [none, enter]
Note: Changing the IP address requires use of the new number when trying to access the web
page. Each meter must be setup with a unique IP address when trying to network multiple units.
When making changes to the IP address, retain the new number for future access.
Z205739-0D
PAGE 41
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
FSRxxxx SERIES
Notes
Forcing this coil on will reset all totalizers. After
reset, the coil automatically returns to the
off state.
Notes
Available Units
Analog Input 1
Gallons, Liters,
Analog Input 2
MGallons, Cubic Feet,
Cubic Meters, Acre
Analog Input 3
Feet, Oil Barrel, Liquid
Barrel, Feet, Meters,
Analog Input 4
Lb, Kg, BTU, MBTU,
MMBTU, TON, kJ, kW,
MW
Analog Input 5
Per Second, Minute,
Hour, Day
Analog Input 6
ºC
Analog Input 7
ºC
Binary Output 1
Writing an (1)
active state to this
object will reset
all totalizers. The
Object will then
automatically
return to the (0)
inactive state.
©2013 Veris Industries
INSTALLATION GUIDE
TFX
Device Configuration
BACnet Device ID: 100
Edit
Location
Enter location information here
Edit
Network Settings
IP Address:
192.168.0.100
Subnet Mask:
255.255.255.0
Gateway IP Address:
0.0.0.0
Edit
Network Status
MAC Address:
00:40:9D:00:00:00
Software Revision:
1.08
Link Duplex:
FULL
Link Speed:
100 MBPS
Diagnostics
Diagnostics Web Page
The Diagnostics web page refreshes itself every 5 seconds and provides real time data
from the meter.
Diagnostics
Main Page
Device Values
Signal Strength
22.8
Flow Rate
100.4
Net Totalizer
1659.1
Positive Totalizer
1659.1
Negative Totalizer
0.0
Temp 1
26.5
Temp 2
48.7
This page will automatically refresh every 5 seconds
Reset Totalizers
Main Page