Veris Industries FSR Series Installation Manual page 42

Ultrasonic flow meter
Table of Contents

Advertisement

TM
BACnet® Object Support
Nine BACnet standard objects are supported, a Device object (DEx), a Binary Output
object (BO1), and seven Analog Input objects (AI1 through AI7). The BACnet/IP UDP
port defaults to 0xBAC0. The Object Identifier (BACnet Device ID) and Location can
both be modified through the web page interface.
Defaults to DEx
DEx
Object_Identifier
Can modify "x" through web page (1-9999)
Object_Name
Up to 32 characters
Object_Type
DEVICE (8)
System_Status
OPERATIONAL or NON_OPERATIONAL
Vendor_Name
"Racine Federated Inc."
Vendor_Identifier
306
Model_Name
"D(X)TFX"
Application_Software_
"1.07"
Version
"Sample Device Location"
Location
Up to 64 characters - can modify through
Protocol_Version
1
Protocol_Revision
2
{ readProperty, writeProperty,
Protocol_Services_
Supported
Protocol_Object_Types_
{ AnalogInput, BinaryOutput, Device }
Supported
Object_List
DEx, AI1, AI2, AI3, AI4, AI5, AI6, AI7, BO1
Max_APDU_Length_
1476
Accepted
Segmentation_Supported
3 – NONE
APDU_Timeout
3000 default
Number_Of_APDU_
1 default
Retries
Device_Address_Binding
always empty
Database_Revision
0
Table A-3.6 - BACnet® Standard Objects
Z205739-0D
PAGE 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
FSRxxxx SERIES
web page
readPropertyMultiple,
writePropertyMultiple,
deviceCommunicationControl, who-Has,
who-Is }
©2013 Veris Industries
W
W
R
R
R
R
R
R
W
R
R
R
R
R
R
R
R
R
R
R
INSTALLATION GUIDE