Channel 2 - Control Output Configuration [FSR1 Only]
Two independent open collector transistor outputs are included with the non-BTU
flow meter. Each output can be configured independently to "Alarm" for one of the
following. See Alarm Output in Part 3 for output details.
None
Batch / Total
Flow
Signal Strength
Errors
System Configuration
Flow Filtering Output Security
Basic
Display
Channel 1:
4-20mA / Frequency
Flow at 4mA / 0Hz:
0
Gal/M
Flow at 20mA / 1KHz:
400
Gal/M
Calibration/Test
Calibration
4 mA
32
20 mA
3837
Test
Test
4
File Open...
File Save...
Figure 5.7 - Channel 2 Output Choices
None: All alarm outputs are disabled
Batch / Total: Multiplier (Value)
This is the value to which the totalizer accumulates before actuating the control pulse
output and repeating the accumulation. This value includes any exponents that were
entered in the BSC MENU as TOTAL E. See Alarm Output in Part 3
Control 1
Mode:
Batch/Total
Multiplier:
50
Flow
ON (Value): Sets value at which the alarm output will switch from OFF to ON
OFF (Value): Sets value at which the alarm output will switch from ON to OFF
Control 1
Mode:
Flow
O <
Gal/M
50
On>
Gal/M
350
Z205739-0D
PAGE 33
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
FSRxxxx SERIES
Channel 2:
Channel 2:
Control Outputs
Control Outputs
Control 1
Mode:
Flow
Flow
Batch/Total
O <
Gal/M
Flow
50
Sig Strength
Errors
On>
Gal/M
350
Control 2
Mode:
Mode:
Flow
None
O <
Gal/M
50
On>
350
Gal/M
Download
©2013 Veris Industries
Signal Strength
ON (Value) : Sets value at which the alarm output will turn ON
OFF (Value): Sets value at which the alarm output will turn OFF
Control 1
Mode:
Sig Strength
O <
On>
Errors
Alarm outputs on any error condition. See Error Table in the Appendix of this manual.

Setting Zero and Calibration

The software utility contains a powerful multi-point calibration routine that can
be used to calibrate the flow meter to a primary measuring standard in a particular
installation. To initialize the three-step calibration routine, click on the Calibration
button located on the top of the Data Screen. The display shown in Figure 5.8 will
appear.
Calibration (Page 1 of 3) - Zero Flow
1. Make sure flow is at zero.
2. Wait for flow to stabilize.
3. Press <Set> to calibrate the zero offset
Cancel
Current Delta T:
File Open...
File Save...
Figure 5.8 - Calibration Page 1 of 3
The first screen (Page 1 of 3) , establishes a baseline zero flow rate measurement for
the instrument.
Because every flow meter installation is slightly different and sound waves can
travel in slightly different ways through these various installations, it is important to
remove the zero offset at zero flow to maintain the meters accuracy. A provision is
made using this entry to establish "Zero" flow and eliminate the offset.
To zero the flow meter:
1) Establish zero flow in the pipe (ensure that the pipe is full of fluid, turn off
all pumps, and close a dead-heading valve). Wait until the delta-time interval
shown in "Current Delta T" is stable (and typically very close to zero).
2) Click the Set button.
3) Click the Next button when prompted, then click the Finish button on the
calibration screen.
The zeroing process is essential in systems using the FST1, FST2, and FST3
transducer sets to ensure the best accuracy.
INSTALLATION GUIDE
.
-0.43
Set --
-0.88
<Back
Next>
Cancel
05131