Wire Method - Yoshitake DP-100 Series Product Manual

Pilot-operated solenoid valve
Table of Contents

Advertisement

6.2 Wiring method
1. Wiring method differs between the voltages, AC 100 / 110 V and 200 / 220 V. Bind the lead wires of the coil
according to the instruction on the label attached to the coil.
2. In order to prevent disconnection or insulation failure, avoid unnecessarily pulling the lead wires or
subjecting them to excessive load while wiring or use.
3. Use electric wires which have a core of 0.75 mm
4. Install a fuse (3A) to protect the electric circuit. In addition, if the product is used in a fuel supply system,
install a circuit protector of a rated current shown in the following.
Rated current of circuit protector
Model
Rated voltage
10-25A
Nominal
size
32-65A
5. When using a terminal box, do not rotate it to change its posture.
* Failure to follow this notice may cause disconnection or insulation failure.
DP-100, DP-100F, DP-100-C and DP-100F-C
AC 100 / 110 V
0.5
0.75-1
AC 100 / 110 V
AC 200 / 220 V
2
or more.
AC 200 / 220 V
0.3
0.5
Switch
Power
12
DP-100-D and
DP-100F-D
DC 24 V
2
Circuit
Fuse
■EPDT-247i■
[A]
Coil