Danfoss Turbocor TTS Series Service Manual page 275

Twin-turbine centrifugal series compressors
Hide thumbs Also See for Turbocor TTS Series:
Table of Contents

Advertisement

Figure B-24 Compressor Voltage Troubleshooting Flowchart (Sheet 3)
B
Electrically isolate 
compressor – Refer 
to Electrical Isolation 
1.7
Remove Top Cover
Remove DC Bus Test 
Harness and re‐
install the J2 and J3 
outputs to DC‐DC
Re‐install Top Cover 
and remove Service 
Side Cover
Re‐apply mains 
power
Verify the HV+ and 
24VDC test points 
on Backplane
Both voltages 
within +/‐ 10%?
Yes
No
Electrically isolate 
compressor
Remove all 
connectors from 
Backplane, leaving 
only the J6 (IGBT 
cable), J4 (250VDC), 
and J24(VDC) inputs 
connected
Remove Serial 
Driver, BMCC, and 
PWM
Re‐apply mains 
power
Verify the HV+ and 
24V test points on 
Backplane
Are voltages 
Yes
within +/‐ 10%?
No
Replace DC‐DC
Verify the +17V +5 
and the ‐15 and +15 
voltage and 
resistance values
Replace Backplane
Are all voltages 
No
within +/‐ 10%?
Yes
Electrically isolate 
compressor
End
Re‐install all 
connectors and the 
PWM, BMCC and 
Serial Driver to 
Backplane
Re‐apply 
compressor power
Verify the +17V, 
+15V, +5 and ‐15 
voltages
Are all voltages 
No
within +/_ 10%?
Yes
If any of the voltages 
are not within +/‐ 
10% refer to Section 
5.5.2 "Determine 
the Cause of an 
Energy Drain."
M-SV-001-EN Rev. G
275 of 282