MANEUROP® RECIPROCATING COMPRESSORS Features The Maneurop® NTZ series from A liquid injection system is not re- Danfoss Commercial Compressors quired. All components are of high is a range of hermetic reciprocating quality and precision to assure a long compressors for low evaporating tem- product life.
At the publication date of this do- sors are according to the standard cument NTZ compressors are only (for ordering Danfoss numbering system. Below available with motor voltage code 4. tables list the code numbers for NTZ For other motor voltage codes, please compressors in single packs and check the availability.
ELECTRICAL CONNECTIONS AND WIRING Voltage application range Motor voltage code Nominal voltage Voltage application range 208-230 V / 1 / 60 Hz 187 – 253 V 200-230 V / 3 / 60 Hz 180 – 253 V 400 V / 3 / 50 Hz 360 –...
ELECTRICAL CONNECTIONS AND WIRING Three phase motor Three phase compressors are inter- current overload and locked rotor nally protected by a temperature / conditions. If the motor were to be protection and current-sensing bimetallic protector, overloaded and the protector trips, all suggested wiring connected to the neutral point of 3-phases are cut out.
R404A and R507A are espe- thermodynamic properties than cially suitable for low and medium R404A and R507A. Especially their temperature applications. Danfoss larger temperature glide shall not be recommends the use of these refrige- neglected. Using these refrigerants the rants with NTZ compressors.
For guidelines on manifolding ternating power supply. Danfoss does Maneurop® NTZ compressors, please not warrant the compressors for use refer to literature called "Parallel Appli- on mobile applications such as trucks, cation Guidelines".
Page 13
For servicing of existing installations refrigerating capacity and the system where acid formation is present the refrigerant charge. Danfoss DCL solid core filter driers Suction pressure control An MOP-type expansion valve or suc- When compressors are mounted onto tion pressure regulator (i.e. Danfoss...
SYSTEM DESIGN RECOMMENDATIONS Operating limits High pressure A high-pressure (HP) safety switch is ted with a manual reset device to pre- required to shut down the compressor vent cycling around the high pressure should the discharge pressure exceed limit. the values shown in the table below. If a discharge valve is used, the HP This switch can be set at lower values switch must be connected to the ser-...
SYSTEM DESIGN RECOMMENDATIONS des the thermostat, mounting bracket indicated below at no more than and insulation. The thermostat must 150 mm from the discharge connec- be attached to the discharge line as tion. Thermostat Discharge line Insulation Bracket Liquid refrigerant control Refrigeration compressors are basi- Liquid refrigerant will dilute the oil, cally designed as gas compressors.
Page 17
floodback both at start-up and during lator manufacturer recommendations. operation or after the defrost opera- As a general rule, Danfoss Commercial tion. This device also helps protect Compressors recommends to size the against off-cycle migration by means...
SOUND AND VIBRATION MANAGEMENT Sound Compressors in operation are one of a refrigeration system. Both pheno- the sources of sound and vibration in mena are closely related. Sound produced by a compressor is quire no external cooling they can be transmitted in every direction by the insulated or enclosed in a sound proo- ambient air, the mounting feet, the...
INSTALLATION AND SERVICE System cleanliness System contamination is one of the parts before brazing and always purge main factors that affects equipment nitrogen or CO through the pipes reliability and compressor service life. during brazing to prevent oxidation. Therefore it is important to take care If flux is used, take every precaution of the system cleanliness when assem- to prevent leakage into the piping.
INSTALLATION AND SERVICE Compressor connection New compressors have a protective or valves may be brazed to the pipes to the system nitrogen holding charge. Only remove when mounted on the compressor. In the suction and discharge plugs just this situation nitrogen or CO must be before connecting the compressor to purged through the compressor via...
INSTALLATION AND SERVICE Leak detection Whenever possible the compressor gen, dry air or acetylene as these gas- must be kept isolated from the sys- ses can form an inflammable mixture tem during leak detection by closing with the compressor oil. Never use CFC the suction and discharge valves Use or HCFC refrigerants for leak detection a mixture of nitrogen and the final re-...
Page 22
Normally denser installations an oil separator is the quantity of oil added should be no recommended. Always use Danfoss more than 2% of the total refrigerant 160Z lubricant for systems with NTZ charge. This percentage does not take compressors and R404A or R507A.
Page 24
Danfoss Commercial Compressors http://cc.danfoss.com Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material.Danfoss reserves the right to alter its products without notice.This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.