Figure 1-15 DC Bus Test Harness Connection Diagram (Closed-Top Soft Start)
Figure 1-16 Cable Passage
24 of 282
M-SV-001-EN Rev. G
Soft Start
(Top Side)
Soft Start
(Top Side)
3.
Connect the two (2) plugs of the DC bus test harness into the Soft Start. Refer to "Figure 1-13
Soft Start (Closed Top)".
4.
Route the cables through the cable passage on either side of the DC-DC Converter, down into
the service side. Refer to "Figure 1-16 Cable Passage" on page 24.
• For clarity purposes, several components have been removed from "Figure 1-16 Cable Passage"
• If the main housing has two cable passages, either passage can be used
5.
Carefully adjust the connectors and harness so that the Top Cover can be reinstalled.
6.
Reinstall the Top Cover and Mains Input Cover. Refer to "4.2 Compressor Covers" on page 56.
7.
Remove ESD strap from the compressor and yourself.
ORIGINAL CONNECTIONS
Harness to DC Bus and AC Line
J1
J7
Harness to DC-DC Converter
CONNECTIONS WITH DC BUS TEST HARNESS
Harness to DC Bus and AC Line
J1
J7
NOTE
Harness to DC-DC Converter
00.0
Volt
Meter
Cable Passage