Danfoss Turbocor TTS Series Service Manual page 272

Twin-turbine centrifugal series compressors
Hide thumbs Also See for Turbocor TTS Series:
Table of Contents

Advertisement

Figure B-21 Compressor Operation Troubleshooting Flowchart (Sheet 2)
B
No
Is DC Bus voltage is 
within spec
Yes
No
Refer to Section 
4.14.2 "Soft Start 
Verification"
Refer to Section 
4.23.2 "DC‐DC 
Verification"
Refer to Section 4.5 
Troubleshooting"
272 of 282
M-SV-001-EN Rev. G
C
Yes
Are I/O cable and 
BMCC board securely 
connected?
Yes
No
Disconnect power, 
secure 
component(s)
A
Refer to Section 
4.26.2 "BMCC 
Verification"
"Voltage 
D
E
F
No
No
Yes
Is 
there a demand % 
displayed?
No
Restore demand 
input to the 
compressor
Close interlock 
A
circuit
Wait until IGV reset 
A
No
Refer to Section 
5.5.4 
"Troubleshooting 
the Inverter"
End
G
Yes
Yes
Yes
 fault be reset by 
cycling the power?
Refer to Section 5.0 
"Troubleshooting"
End
Note the IGV settings
Has 
the IGV reset?
Yes
No
Is Inverter Temp 
below Maximum Start 
Temp?
Yes
Have all Start Delay 
Timers have expired?
Yes
A
H
No
Can
No
No
Wait until all Start 
Delay Timers have 
expired