Versions; Two-Wire Version; Version; Device Overview And Operating Controls - Samson Media 7 5007-1 Mounting And Operating Instructions

Differential pressure meter with remote data transmission
Table of Contents

Advertisement

Design and principle of operation

3.2 Versions

3.2.1

Two-wire version

− Type 5007-1-000x...
To operate the two-wire version, a trans-
mitter supply voltage for the 4 to 20 mA
current loop is required (U
36 V DC for the version without explo-
sion protection).
− Type 5007-1-1xx0....
To operate the two-wire version, a trans-
mitter supply voltage for the 4 to 20 mA
current loop is required (U
28 V DC for the version with explosion
protection).
The current loop must be supplied only
by a supply unit which has an equivalent
or higher explosion protection approval.
Its electrical connection data must be
lower or identical to those in the explo-
sion protection certificate of the
Type 5007-1-1xx0.. device.
3.2.2
24 V version
− Type 5007-1-xxx1...
The 24 V version has a wider ambient
temperature range. Due to a more pow-
erful input signal, it has additional func-
tions, such as an illuminated display and
remote data transmission through the use
of a retrofittable GSM module.
3-4
3.2.3
− Type 5007-1-xxx2...
= 12 to
B
3.3 Device overview and oper-
Î See Fig. 3-4
1
= 12 to
2
B
3
4
5
6
7
8
9
10 Slot for GSM module
11 SSP interface
12 Slots 1 to 4 for option modules
13 SPS: standby power supply
14 Grounding connection
230 V version
Due to a more powerful input signal, the
230 V version has additional functions,
such as an illuminated display and re-
mote data transmission through the use
of a retrofittable GSM module.
ating controls
Display
Confirm key
Up arrow key
Down arrow key
Back key
Error LED
Battery LED (SPS)
Status LEDs for GSM module
Signal input terminal
EB 9510 EN