Victron energy CCGX Manual page 5

Generator auto start/stop
Hide thumbs Also See for CCGX:

Advertisement

2020-11-11 18:41
a consumption peak and go back to a normal value in a few seconds. In this kind of situations
the start of the generator is usually not desired. This option will delay the generator start until
the start value is reached for a minimum amount time.
Stop when "condition" is higher than: The same than above but for stop value.
Stop value during quiet hours: The same than above but for stop value.
Stop after the condition is reached for: The same than above but for stop value.
* Higher/lower value depends on the type of condition.
AC load condition
AC load condition works like the rest of conditions but has the "Measurement" extra setting.
The "Measurement" setting is available on firmware v2.0 and onwards and has three possible values:
Total consumption (Default option)
Inverter total AC out
Inverter AC out highest phase
Test run condition
Allows you to program a periodical test run.
Test run interval: Test run will be performed periodically based on this setting
Skip test run if has been running for: The test will be skipped if during the test run interval
the generator was running at least the number of hours set on this setting.
Victron Energy - https://www.victronenergy.com/live/
5/8
GX - Generator auto start/stop