Generator auto start/stop
Hide thumbs Also See for CCGX:

Advertisement

2020-11-11 18:41
Conditions: See
Minimum runtime: Once started the generator should run for a minimum amount of time, for
manual start this setting is ignored.
Detect generator at AC input: After starting the generator, it monitors the Multi (or Quattro),
to see if it connects to the generator. In case it does not it will cause an alarm. This function
catches a wide array of possible problems, like a simple no fuel situation, but also a tripped fuse
or other problem between the generator and the Quattro. This functionality is not available for
VE.Can connected Multi/Quattro.
Quiet hours: See
Reset daily run time counters: Reset the last 30 days run time counters.
Generator total run time: Sets the total run time counter.
Conditions
Conditions location: Generator start and stop → Settings → Conditions
* Battery monitor: Select which battery monitor will be used for DC related conditions.
* On loss of communication: Defines the behavior when the datalink between the CCGX/Venus GX
and the selected battery monitor and/or vebus inverter/charger is lost. Options are:
Stop the generator: If the generator is running and the datalink is lost, the generator will be
Victron Energy - https://www.victronenergy.com/live/
3/8
Conditions
Quiet hours
GX - Generator auto start/stop