Lutron Electronics Maestro MS-OPS2 1 Series Manual page 22

Switch with occupancy/ vacancy sensor
Table of Contents

Advertisement

Maestro
Wiring Diagrams
Wiring Diagram 11 - with Neutral
Multi-Location Installation (277 V~)
-OPS6M2U-DV, -VPS6M2U-DV with MA-AS-277 or MSC-AS-277
MA-AS-277 or
MSC-AS-277
Hot / Live
Black
Green
277 V~
50 / 60 Hz
Ground
Neutral
Note: When a neutral connection is available, connect the white-sleeved wire to neutral.
Wiring Diagram 11 - without Neutral
Multi-Location Installation (277 V~)
-OPS6M2U-DV, -VPS6M2U-DV with MA-AS-277 or MSC-AS-277
MA-AS-277 or
MSC-AS-277
Hot/Live
Black
Green
277 V~
50 / 60 Hz
Ground
Neutral
Note: Remove white sleeve and connect green wire to ground only in retrofit and replacement applications.
1
A single standard mechanical 3-way switch or up to 9 companion switches may be connected to most occupancy sensor switches.
Standard mechanical 3-way switch cannot be combined with companion switch. Total blue terminal wire length may be up to 150 ft (46 m).
2
Only one occupancy sensor switch can be used per multi-location circuit.
3
Occupancy sensor switch can be installed in any location.
4
Fan load applies to 120 V~ only (not for 277 V~).
S P E C I F I C AT I O N S U B M I T TA L
®
Job Name:
Job Number:
Switch with Occupancy / Vacancy Sensor
(continued)
1, 2, 3, 4
MA-AS-277 or
MSC-AS-277
Blue
Red
Black
Green
1, 2, 3, 4
MA-AS-277 or
MSC-AS-277
Blue
Red
Black
Green
Model Numbers:
Blue
Red
Black
Bare
Ground
Blue
Black
Red
Bare
Ground
Occupancy
sensor switch
3
Blue
Black
White-
sleeved
wire
Load
Ground
Occupancy
3
sensor switch
Blue
Black
Green
Load
Ground
Sensor
369666f 22 09.05.19
Continued on next page...
Page
22

Hide quick links:

Advertisement

Table of Contents
loading