Lutron Electronics Maestro MS-OPS2 1 Series Manual page 15

Switch with occupancy/ vacancy sensor
Table of Contents

Advertisement

Maestro
Wiring Diagrams
Wiring Diagram 6 - with Neutral
Multi-Location Installation (277 V~)
-OPS6M2-DV, -VPS6M2-DV with MA-AS-277 or MSC-AS-277
MA-AS-277 or
MSC-AS-277
Hot / Live
Black
Green
277 V~
50 / 60 Hz
Ground
Neutral
Note: When a neutral connection is available, remove the green sleeve and connect the white wire to neutral.
Wiring Diagram 6 - without Neutral
Multi-Location Installation (277 V~)
-OPS6M2-DV, -VPS6M2-DV with MA-AS-277 or MSC-AS-277
MA-AS-277 or
MSC-AS-277
Hot / Live
Black
Green
277 V~
50 / 60 Hz
Ground
Neutral
Note: Connect green-sleeved wire to ground only in retrofit and replacement applications.
1
A single standard mechanical 3-way switch or up to 9 companion switches may be connected to most occupancy sensor switches.
Standard mechanical 3-way switch cannot be combined with companion switch. Total blue terminal wire length may be up to 150 ft (46 m).
2
Only one occupancy sensor switch can be used per multi-location circuit.
3
Fan load applies to 120 V~ only (not for 277 V~).
4
Occupancy sensor switch can be installed in any location.
S P E C I F I C AT I O N S U B M I T TA L
®
Job Name:
Job Number:
Switch with Occupancy / Vacancy Sensor
(continued)
1, 2, 3, 4
Blue
Black
Red
1, 2, 3, 4
Blue
Red
Black
Model Numbers:
MA-AS-277 or
MSC-AS-277
Blue
Red
Green
Ground
MA-AS-277 or
MSC-AS-277
Blue
Red
Green
Ground
Occupancy
3
sensor switch
Blue
Black
Black
White
Bare
Ground
Occupancy
sensor switch
3
Blue
Black
Black
Bare
Green-
sleeved
wire
Ground
Continued on next page...
Sensor
369666f 15 09.05.19
Load
Load
Page
15