Lutron Electronics Maestro MS-OPS2 1 Series Manual page 11

Switch with occupancy/ vacancy sensor
Table of Contents

Advertisement

Maestro
Wiring Diagrams
Wiring Diagram 3 - without Neutral
3-way Installation with Standard Mechanical Switch (120 V~)
-OPS5M, -OPS6M2-DV, -VPS5M, -VPS6M2-DV
Hot/Live
Jumper wire
120 V~
50 / 60 Hz
Neutral
OR
Hot/Live
120 V~
50 / 60 Hz
Neutral
Note: Connect green-sleeved wire to ground only in retrofit and replacement applications.
1
When using controls in single location installations, tighten the blue terminal or cap blue wire. Do not connect the blue terminal / wire to any other
wire or to ground.
2
Only one occupancy sensor switch can be used per multi-location circuit.
3
A single standard mechanical 3-way switch or up to 9 companion switches may be connected to most occupancy sensor switches.
Standard mechanical 3-way switch cannot be combined with companion switch. Total blue terminal wire length may be up to 150 ft (46 m).
S P E C I F I C AT I O N S U B M I T TA L
®
Job Name:
Job Number:
Switch with Occupancy / Vacancy Sensor
(continued)
Standard
mechanical switch
Different color
screw (Common)
Green
screw
Ground
Occupancy
sensor switch
Black
Black
Blue
Green-sleeved wire
Bare
Ground
Model Numbers:
2, 3
Occupancy
sensor switch
Black
Black
Blue
Green-sleeved wire
Bare
Ground
Standard
mechanical switch
Different color
screw (Common)
Jumper wire
Green
screw
Ground
Sensor
369666f 11 09.05.19
Load
Load
Continued on next page...
Page
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents