Installation of the HVI

holder distance of 1000 mm; wall distance of 240 mm

Metal conductor holders of type HVI
(Part No. 275 455) and a maximum installation distance of ≤ 1000 mm (see Fig. 6) reliably prevent
discharges. The conductor holders are fixed via pipe clamps (Part No. 106 323; see Fig. 7, page 10).
PD of 240 mm
Figure 6
Conductor holders of type HVI
PD of 85 mm
®
HVI
power Conductor
HD 500 mm
power Ex P85 holder for HVI
®
®
power Conductor in parallel to an earthed metal pipe,
power Ex P240 holder, with a pipe distance (PD) of 240 mm
®
HVI
power Conductor
®
HD of 1000 mm
power Ex P240 holder for HVI
®
power Conductors (Part No. 275 454)
®
power Conductors (Part No. 275 455)
®
9