Holder Distance Of 500 Mm; Wall Distance Of 85 Mm; Installation Of The Hvi - dehn HVI power Conductor Installation Instructions Manual

Lightning protection/earthing
Hide thumbs Also See for HVI power Conductor:
Table of Contents

Advertisement

Available languages

Available languages

2.5

Installation of the HVI

holder distance of 500 mm; wall distance of 85 mm

Fig. 4 shows a typical application at a metal pipe, e.g. a mobile phone mast.
If metal conductor holders of type HVI
(Part No. 275 454) and a maximum installation distance ≤ 500 mm (see Fig. 4) are used, discharges can
be reliably prevented. The conductor holders are fixed by means of a pipe clamp (Part No. 106 323; see
Fig. 7, page 10).
Conductor holder of type HVI
P85 holder for HVI
(Part No. 275 454) for earthed metal pipes
with a diameter between 50 and 300 mm.
Figure 4
Installation in parallel to an earthed metal pipe: holder distance of 500 mm; pipe distance of 85 mm
8
®
power Conductor in parallel to an earthed metal pipe,
power Ex P85 holder with a pipe distance (PD) of 850 mm
®
power Ex
®
power Conductors
®
Ex zone 22
Ex zone 21
ceiling profile
exhaust opening on the silo roof
α
α
S
Ex zone 20
sealing end
HD 500 mm installation distance
HVI
EB
EB = earthing busbar
power Conductor
®