Troubleshooting; Warnings And Alarms - Danfoss VLT Micro Drive FC 51 Series Quick Manual

Hide thumbs Also See for VLT Micro Drive FC 51 Series:
Table of Contents

Advertisement

Quick Guide

1.6 Troubleshooting

1.6.1 Warnings and Alarms

No. Description
2
Live zero error
4
1
Mains phase loss
)
7
1
DC overvoltage
)
8
1
DC undervoltage
)
9
overloaded
10
Motor overtemperature
11
Motor thermistor overtemp.
12
Torque limit
13
Overcurrent
14
Ground fault
16
Short circuit
17
Control word timeout
25
Brake resistor short-circuited
27
Brake chopper short-circuited
28
Brake check
29
Power board overtemp
30
Motor phase U missing
31
Motor phase V missing
32
Motor phase W missing
38
Internal fault
44
Ground fault
47
Control Voltage Fault
51
check U
and I
nom
nom
52
low I
nom
59
Current limit
63
Mechanical Brake Low
80
84
The connection between drive
and LCP is lost
85
Button disabled
86
Copy fail
87
LCP data invalid
88
LCP data not compatible
89
Parameter read-only
90
Parameter database busy
91
Parameter value is not valid in this
mode
92
Parameter value exceeds the
min/max limits
nw
Not While RUNning
run
Err. An incorrect password was
entered
1)
These faults may be caused by line power distortions. Installing a Danfoss line filter may rectify this problem.
Table 1.6 Warnings and Alarms Code List
MG02B922
Quick Guide
Warning Alarm
Trip
Error
Lock
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
Cause of Problem
Signal on terminal 53 or 60 is less than 50% of value set in
6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Currentand
6-22 Terminal 54 Low Current.
Missing phase on the supply side, or a voltage imbalance that is too
high. Check supply voltage.
Intermediate circuit voltage exceeds the limit.
Intermediate circuit voltage drops below the "voltage warning low"
limit.
More than 100% load for too long.
Motor is too hot due to more than 100% load for too long.
The thermistor or the thermistor connection is disconnected.
Torque exceeds value set in either parameter 4-16 Torque Limit
Motor Mode or 4-17Torque Limit Generator Mode.
current limit is exceeded.
Discharge from output phases to ground.
Short-circuit in the motor or on the motor terminals.
No communication to the adjustable frequency drive.
Brake resistor is short-circuited, thus the brake function is discon-
nected.
Brake transistor is short-circuited, thus the brake function is discon-
nected.
Brake resistor is not connected/working
Heatsink cut-out temperature has been reached.
Motor phase U is missing. Check the phase.
Motor phase V is missing. Check the phase.
Motor phase W is missing. Check the phase.
Contact local Danfoss supplier.
Discharge from output phases to ground.
24 V DC may be overloaded.
Wrong setting for motor voltage and/or motor current.
Motor current is too low. Check settings.
overload.
Actual motor current has not exceeded the "release brake" current
in the "start delay" time window.
No communication between LCP and adjustable frequency drive
See parameter group 0-4* 0-4* LCP
An error occurred while copying from adjustable frequency drive to
LCP or vice versa.
Occurs when copying from LCP if the LCP contains erroneous data -
or if no data was uploaded to the LCP.
Occurs when copying from LCP if data are moved between
adjustable frequency drives with major differences in software
versions.
Occurs when trying to write to a read-only parameter.
LCP and RS485 connection are trying to update parameters simulta-
neously.
Occurs when trying to write an illegal value to a parameter.
Occurs when trying to set a value outside the range.
Parameter can only be changed when the motor is stopped.
Occurs when using an incorrect password for changing a password-
protected parameter.
1
1
15