Quick Guide
1
1
Relay output
Programmable relay output
Relay 01 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Min. terminal load on 01-03 (NC), 01-02 (NO)
Environment according to EN 60664-1
1)
IEC 60947 part 4 and 5
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
NOTICE!
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure
Enclosure kit available.
Vibration test
Max. relative humidity
Aggressive environment (IEC 60721-3-3), coated
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Derating for high ambient temperature, see chapter 1.9.1 Derating for Ambient Temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see chapter 1.9 Special Conditions
Safety standards
EMC standards, Emission
EMC standards, Immunity
See chapter 1.9 Special Conditions
20
Quick Guide
1)
on 01-02 (NO) (resistive load)
1)
on 01-02 (NO) (Inductive load @ cosφ 0.4)
1)
on 01-02 (NO) (resistive load)
1)
on 01-02 (NO) (inductive load)
1)
on 01-03 (NC) (resistive load)
1)
on 01-03 (NC) (Inductive load @ cosφ 0.4)
1)
on 01-03 (NC) (resistive load)
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
Overvoltage category III/pollution degree 2
5–95% (IEC 60721-3-3); Class 3K3 (non-condensing) during operation
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
01-03 (break), 01-02 (make)
250 V AC, 2 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 2 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC 10 mA, 24 V AC 20 mA
10.5 V ±0.5 V
25 mA
IP20
IP21, TYPE 1
1.0 g
class 3C3
Max. 104°F [40°C]
32°F [0°C]
14° [-10°C]
-13°–+149/158°F [-25°–+65/70°C]
3300 ft [1000 m]
10,000 ft [3000 m]
EN/IEC 61800-5-1, UL 508C
MG02B922
1
50