Electrical connection

6.6 Laying the signal lines

6.6
Laying the signal lines
Malfunction due to common cable installation
Malfunctions can occur in the converter if cables with differing voltage levels are laid together
with internal cables in one cable duct in the cabinet.
● Do not run cables coming from the outside, for example to the terminal strips, together with
Ensure that the following instructions are complied with:
● All signal lines must be shielded. The cable shield should be braided, because cables
● Clamp the shield of incoming analog and binary cables to the shield busbar at the entry point
● Serial connecting cables must be shielded. Place the shield on the metallic connector
● The connector housing and front plate of the boards do not provide adequate cable
You should only use the pre-assembled cable sets supplied. These cable sets are marked at
both cable ends with the precise designation of the connection point at which you must connect
or plug in the cable.
Note
For more information, see the interconnection diagram in the circuit manual.
Please proceed as follows:
1. Connect the signal and power supply cables.
2. Connect the shield and secure the cable. You can find further information on this in the
3. Seal the cable routing according to the degree of protection required.
See also
Electromagnetic compatibility (Page 81)
86
internal cables in one cable duct.
shielded by tape or foil are five times less efficiently protected against interference. Always
ground the cable shields at both ends. Contacting at one end is advantageous in
exceptional cases only.
into the cabinet. Continue running the cable, still shielded, to the terminal strip or board. No
shields are connected to the terminal strips or boards.
housing. Also connect the shield to the shield rail. Do not connect the cable shield to a
ground pin of the connector.
shielding. Connect the cable shields at both ends to the shield rails in the cabinets. Always
use shielded analog signal cables, regardless of whether they are installed inside or outside
cabinets. In order to increase the effectiveness of the shielding, ground spare conductors at
both ends.
"Electromagnetic compatibility" section.
SINAMICS PERFECT HARMONY GH150 6SL38253AE412AA1-Z
Operating Instructions Rev.201910281231 EXAMPLE