Table 6.13 Using SLC to Set a Relay
BAS-SVX54B-EN
TR200 D-Frame Operating Instructions
Parameters
Function
Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
100 RPM
Feedback Speed
Error
4-32 Motor
5 s
Feedback Loss
Timeout
7-00 Speed PID
[2] MCB 102
Feedback Source
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start
[19] Warning
Event
13-02 Stop
[44] Reset
Event
key
13-10 Comparat
[21] Warning
or Operand
no.
13-11 Comparat
[1] ≈*
or Operator
13-12 Comparat
90
or Value
13-51 SL
[22]
Controller Event
Comparator 0
13-52 SL
[32] Set
Controller Action
digital out A
low
5-40 Function
[80] SL digital
Relay
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and in the
case that Warning 90 becomes
TRUE then Relay 1 is triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 s then the frequency
converter continues and the
warning disappears. But Relay 1
will still be triggered until
[Reset] on the LCP.
Illustration 6.4 Mechanical Brake Control
Application Examples
53