Trane TR200 Operating Instructions Manual page 55

D-frame, 110-400 kw
Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Application Examples
S p e e d
R e f e r e n c e
S t a r t ( 1 8 )
F r e e z e r e f ( 2 7 )
S p e e d u p ( 2 9 )
S p e e d d o w n ( 3 2 )
Illustration 6.3 Speed Up/Down
Table 6.11 RS-485 Network Connection
52
TR200 D-Frame Operating Instructions
Parameters
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate
9600*
*=Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
Table 6.12 Motor Thermistor
Parameters
Function
Setting
1-90 Motor
[2]
Thermal
Thermistor
Protection
trip
1-93 Thermistor
[1] Analog
Source
input 53
*=Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
BAS-SVX54B-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents