Application Examples
Table 6.4 Analog Speed Reference (Current)
Table 6.5 Start/Stop Command with Safe Stop
50
TR200 D-Frame Operating Instructions
Parameters
Function
Setting
6-12 Terminal 53
4 mA*
Low Current
6-13 Terminal 53
20 mA*
High Current
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
*=Default Value
Notes/comments:
Parameters
Function
Setting
5-10 Terminal 18
[8] Start*
Digital Input
5-12 Terminal 27
[0] No
Digital Input
operation
5-19 Terminal 37
[1] Safe Stop
Safe Stop
Alarm
*=Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
Illustration 6.1 Start/Stop with Safe Stop
Table 6.6 Pulse Start/Stop
Illustration 6.2 Latched Start/Stop Inverse
Parameters
Function
Setting
5-10 Terminal 18
[9] Latched
Digital Input
Start
5-12 Terminal 27
[6] Stop
Digital Input
Inverse
*=Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.