Programming

5 Programming

5.1 Introduction

The frequency converter is programmed for its application
functions using parameters. Parameters are accessed by
pressing either [Quick Menu] or [Main Menu] on the LCP.
(See 4.1 Local Control Panel for details on using the LCP
function keys). Parameters may also be accessed through a
PC using the Trane Drive Utility (TDU) (see 5.6.1 Remote
Programming with ).
The quick menu is intended for initial start up (Q2-** Quick
Set Up) and detailed instructions for common frequency
converter applications (Q3-** Function Set Up). Step-by-step
instructions are provided. These instructions enable the
user to walk through the parameters used for
programming applications in their proper sequence. Data
entered in a parameter can change the options available in
the parameters following that entry. The quick menu
presents easy guidelines for getting most systems up and
running.
The main menu accesses all parameters and allows for
advanced frequency converter applications.

5.2 Programming Example

Here is an example for programming the frequency
converter for a common application in open loop using
the quick menu.
This procedure programs the frequency converter
to receive a 0-10 V DC analog control signal on
input terminal 53
The frequency converter will respond by
providing 20-50 Hz output to the motor propor-
tional to the input signal (0-10 V DC=20-50 Hz)
This is a common pump or fan application.
Press [Quick Menu] and select the following parameters
using the navigation keys to scroll to the titles and press
[OK] after each action.
40
TR200 D-Frame Operating Instructions
1.
2.
Illustration 5.1
3.
Illustration 5.2
4.
Illustration 5.3
5.
Illustration 5.4
Q3 Function Setups
Parameter Data Set
Q3-2 Open Loop Settings
Q3-21 Analog Reference
3-02 Minimum Reference. Set minimum internal
frequency converter reference to 0 Hz. (This sets
the minimum frequency converter speed at 0 Hz).
BAS-SVX54B-EN