Chapter 2 Specifications; Performance Specifications - Mitsubishi Electric MELSEC iQ-R Series User Manual

Profibus-dp module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2
SPECIFICATIONS
2.1

Performance Specifications

The following table lists the performance specifications of the RJ71PB91V.
Item
PROFIBUS-DP station type
Transmis
Electrical standard and characteristics
sion
Medium
specifica
Network configuration
tions
Data link method
Encoding method
*1
Transmission speed
Transmission distance
Number of connectable modules of the
entire network
Number of connectable modules per
segment
Number of repeaters
Transmittable data
Number of occupied I/O points
Internal current consumption (5VDC)
External
Height
dimensio
Width
ns
Depth
Weight
*1 Transmission speed accuracy is within 0.2% (compliant with IEC 61158-2).
Transmission distance
Transmission speed
9.6kbps
19.2kbps
45.45kbps
93.75kbps
187.5kbps
500kbps
1.5Mbps
3Mbps
6Mbps
12Mbps
*1 The maximum transmission distance shown in the above table indicates the distance when three repeaters are used.
To calculate the maximum transmission distance when repeaters are used and the transmission distance is extended, use the following
formula.
Maximum transmission distance [m/network] = (Number of repeaters + 1)  Transmission distance[m/segment]
Description
DP-Master (Class 1)
Compliant with EIA-RS485
Shielded twisted pair cable ( Page 32 Wiring for PROFIBUS cable)
Bus topology (or tree topology when repeaters are used)
• Between DP-Masters: Token passing
• Between DP-Master and DP-Slaves: Polling
NRZ
9.6kbps to 12Mbps ( Page 21 Transmission distance)
Varies depending on the transmission speed. ( Page 21 Transmission distance)
DP-Masters + DP-Slaves  126 modules (When the redundant system is configured, DP-Master of
the control system + DP-Master of the standby system + DP-Slaves  126 modules) ( Page 29
Maximum configuration of network (using three repeaters))
DP-Master + DP-Slave + Repeater  32 (When the redundant system is configured, DP-Master of
the control system + DP-Master of the standby system + DP-Slave + Repeater  32 modules) (
Page 28 Maximum configuration of network (using one repeater))
Maximum of three repeaters between the DP-Master and a DP-Slave (When the redundant system
is configured, maximum of three repeaters between the DP-Master and a DP-Slave of both
systems)
Input data
Maximum of 8192 bytes (maximum of 244 bytes
per DP-Slave)
Output data
Maximum of 8192 bytes (maximum of 244 bytes
per DP-Slave)
32 points
0.42A
106mm (base unit mounting side: 98mm)
27.8mm
110mm
0.16kg
Transmission distance
1200m/segment
1000m/segment
400m/segment
200m/segment
100m/segment
DP-Slave
Maximum of 244 bytes (maximum of 384 bytes
in total of I/O data)
Maximum of 244 bytes (maximum of 384 bytes
in total of I/O data)
Maximum transmission distance when
*1
repeaters are used
4800m/network
4000m/network
1600m/network
800m/network
400m/network
2 SPECIFICATIONS
2.1 Performance Specifications
2
21