This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.
Page 2
Table of Contents 1. Introduction ............................. 2 2. Appearance ............................3 3. Features ............................4 4. Set up Instruction ..........................5 5. Data Report ............................. 6 5.1 Example of ReportDataCmd ..................... 7 5.2 Example of Threshold Alarm ....................9 5.3 Example of ConfigureCmd ..................... 10 5.4 Example of SetRportType ......................11 5.5 Example of SetSensorAlarmThresholdCmd ................
Page 3
1. Introduction The R718N3xxx(E) series is 3-Phase Current Meter device for Netvox Class A type devices based on the LoRaWAN open protocol and is compatible with the LoRaWAN protocol. R718N3xxx(E) series have different measuring range for different variety of CT. It is divided into:...
Page 5
Available third-party platform: Actility/ThingPark, TTN, MyDevices/Cayenne Low power consumption and long battery life Note: Please refer to web: http://www.netvox.com.tw/electric/electric_calc.html. Users can find battery lifetime for various models at different configurations on this website. 1. The actual range may vary depending on the environment.
Page 6
4. Set up Instruction On/Off Power on Insert batteries. (Users may need a screwdriver to open the battery cover.) Turn on Press and hold the function key for 3 seconds until the green indicator flashes once. Turn off (Reset to factory setting) Press and hold the function key for 5 seconds until green indicator flashes 20 times.
Page 7
Current transformer (measurement range > 75A): report data as 0 when the current < 1A. Please refer to Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://www.netvox.com.cn:8888/cmddoc to resolve uplink data. Data report configuration and sending period are as following: Current Change<...
Page 8
5.1 Example of ReportDataCmd FPort:0x06 Bytes Var (Fix=8 Bytes) Version DeviceType ReportType NetvoxPayLoadData Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version DeviceType– 1 byte – Device Type of Device ReportType – 1 byte –the presentation of the NetvoxPayLoadData, according the devicetype NetvoxPayLoadData–...
Page 9
byte (01): Version byte (4A): DeviceType - R718N3xxx(E) Series byte (01): ReportType byte (9F): Battery – 3.1V (low voltage), 9F (Hex) = 1001 1111(Bin) >> 1F(Hex) =31(Dec), 31*0.1v=3.1v // if bit 7= 1, it means low voltage. byte (05DD): Current1 –05DD (Hex) = 1501 (Dec), 1501* 1mA = 1501mA byte (05D4): Current2 –...
Page 10
Uplink: Packet: 014A039F05DD05D436B010 byte (01): Version byte (4A): DeviceType- R718N3xxx(E) Series byte (03): ReportType byte (9F): Battery-3.1V (low voltage), 9F (Hex) = 1001 1111(Bin) >> 1F(Hex) =31(Dec), 31*0.1v=3.1v // if bit 7= 1, it means low voltage. byte (05DD): Current1 –05DD (Hex) = 1501 (Dec), 1501* 1mA = 1501mA byte (05D4): Current2 –...
Page 11
5.3 Example of ConfigureCmd FPort:0x07 Bytes Var(Fix =9 Bytes) CmdID DeviceType NetvoxPayLoadData CmdID– 1 byte DeviceType– 1 byte – Device Type of Device NetvoxPayLoadData– var bytes (Max=9bytes) Device Description Device CmdID NetvoxPayLoadData Type Config MinTime MaxTime CurrentChange Reserved 0x01 ReportReq (2bytes Unit:s) (2bytes Unit:s) (2byte Unit:1mA)
Page 12
5.4 Example of SetRportType FPort:0x07 Set the R718N3xxx(E) data to send either one or two packets. Device Description Device NetvoxPayLoadData CmdID Type ReportTypeSet (1Byte) Reserved SetRportTypeReq 0x03 0x00_reporttype1&2 (8Bytes,Fixed 0x00) 0x01_reporttype3 Status Reserved SetRportTypeRsp 0x83 R718N3xxx(E) (8Bytes,Fixed 0x00) (0x00_success) 0x4A Series Reserved GetRportTypeReq...
Page 13
5.5 Example of SetSensorAlarmThresholdCmd Fport:0x10 CmdID CmdDescriptor Payload (10Bytes) (1Byte) Channel(1Byte) SensorType(1Byte) SetSensorAlarm 0x00_Channel1 SensorHighThreshold SensorLowThreshold 0x01 0x00_Disable ALL ThresholdReq 0x01_Chanel2 (4Bytes,Unit:1mA) (4Bytes,Unit:1mA) 0x27_Current 0x02_Channel3 SetSensorAlarm Status Reserved 0x81 ThresholdRsp (0x00_success) (9Bytes,Fixed 0x00) Channel(1Byte) SensorType(1Byte) GetSensorAlarm 0x00_Channel1 Reserved 0x02 0x00_Disable ALL ThresholdReq 0x01_Chanel2 (8Bytes,Fixed 0x00)
Page 14
(3) Disable all sensor thresholds for channel 1. Configure the Sensor Type to 0 Downlink: 0100000000000000000000 Response: 8100000000000000000000 5.6 Example of NetvoxLoRaWANRejoin Check if the device is still in the network. If the device is disconnected, it will automatically rejoin back to the network. Fport: 0x20 CmdID Payload (5 bytes)
Page 15
5.7 Example for MinTime/MaxTime logic Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V MaxTime MaxTime sleeping (MinTime) sleeping (MinTime) Wakes up and collect data Wakes up and collect data Wake up and collect data REPORTS 3.6V REPORTS 3.6V REPORTS 3.6V...
Page 16
Notes : 1) The device only wakes up and performs data sampling according to MinTime Interval. When it is sleeping, it does not collect data. 2) The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the device reports according to MinTime interval.
Page 17
6. Installation 4. The 3-phase current meter samples the current according to 1. The 3-phase current meter R718N3xxx(E) series has a MinTime. If the current value sampled this time relatively built-in magnet (see Figure 1 below). It can be attached exceeds the set value (the default is 100mA) more than the to the surface of an object with iron during installation, current value reported last time, the device will immediately...
Page 18
Current Direction The CT terminal should be close to the power terminal as much as possible. R718N3xxx(E) Phase A Screw Wire to be Fixation detected Screw Fixation Current Direction Current Direction Phase B Phase C The CT terminal should be Wire to be The CT terminal should be Wire to be...
Page 19
If the live wire and the neutral wire are connected together at the same time, they will offset each other and the measurement is 0. Neutral Wire L ← K Live Wire Note: 1. Please do not disassemble the device unless it is required to replace the batteries. 2.
Page 20
7. Information about Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density. However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high.
Page 21
8. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: •Do not put the device near or submerge into water. Minerals in rain, moisture, and other liquids could cause corrosion of electronic components.