Example of ConfigureCmd
FPort:0x07
Bytes
1
CmdID
CmdID– 1 bytes
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
Report configuration:
Description
Device
ConfigReport
Req
ConfigReport
Rsp
R718N1
ReadConfig
ReportReq
ReadConfig
ReportRsp
(1) Configure report parameters MinTime = 15min, MaxTime = 15min, CurrentChange = 100mA
Downlink: 0149038403840064000000
The device returns:
8149000000000000000000 (Configuration succeeded)
8149010000000000000000 (Configuration failed)
(2) Read device configuration parameters
Downlink: 0249000000000000000000
The device returns:
8249038403840064000000 (current device configuration parameters)
1
DeviceType
Cmd
Device
ID
Type
MinTime
0x01
(2bytes Unit:s)
0x81
0x49
0x02
MinTime
0x82
(2bytes Unit:s)
Var(Fix =9 Bytes)
NetvoxPayLoadData
NetvoxPayLoadData
MaxTime
(2bytes Unit:s)
Status
(0x00_success)
(9Bytes,Fixed 0x00)
MaxTime
(2bytes Unit:s)
7
CurrentChange
(2byte Unit:1mA)
(3Bytes,Fixed 0x00)
Reserved
(8Bytes,Fixed 0x00)
Reserved
CurrentChange
(2byte Unit:1mA)
(3Bytes,Fixed 0x00)
Reserved
Reserved