Functional Description - AEG Thyro-E Series Operating Instructions Manual

Lighting controller
Table of Contents

Advertisement

Operations Manual Thyro Power Manager

Functional Description

The power controller is provided with an overvoltage and undervoltage monitor. If the lamp
voltage falls below the adjustable value (factory setting 180V, see chapter 8.1.2 on page 33),
it is immediately switched to the next higher stage. An extinguishing of the lamps is thereby
prevented.
If the lamp voltage exceeds an adjustable value (factory setting 250V, see chapter 8.1.2 on
page 33), it is immediately switched to the next lower stage thereby counteracting a
reduction of life.
7.2
Functional Description
The full supply voltage is switched through to the lamps for an adjustable time after
connecting the system.
This step is necessary to guarantee a normal warming-up of the lamps. After expiration of
this time, it is automatically switched to the stage required by the user. In many cases, the
starting current significantly exceeds the nominal current of the lighting system. This fact has
to be taken into consideration during the design phase.
Figure 13: Connection and Reduction of a Car Park Lighting with HQL Lamps
8000022632 BAL, EN
Version: 1.7.2009