AMS P
SERIES R32
EN
INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS

Advertisement

Table of Contents
loading

Summary of Contents for Riello AMS P Series

  • Page 1 AMS P SERIES R32 INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS...
  • Page 2 While your technical skills and knowledge will certainly be more than sufficient, this booklet contains all the information that we have deemed necessary for the device's correct and easy installation. Thank you again, and keep up the good work. RIELLO COMPLIANCE R AMS P heat pumps are compliant with the following European Directives: —...
  • Page 3: Table Of Contents

    AMS P TAbLE OF CONTENTS GENERAL INFORMATION ....p. 4 General Notices ......p. 4 Safety precautions .
  • Page 4: General Information

    GENERAl INfORMAtION GENERAL INFORMATION According to EU Regulation no. 517/2014 regarding certain General Notices fluorinated greenhouse gases, the total amount of refrig- erant contained within the installed system must be indi- cated. This information can be found on the unit technical data plate.
  • Page 5: Unit Description

    GENERAl INfORMAtION Unit description Identification R AMS P is an indoor unit for ceiling or floor installation, The unit can be identified through the technical data plate: suitable for use commercial premises in combination with the outdoor unit. The multiple-speed fan DC motor improves per- formance and sound comfort.
  • Page 6: Technical Specifications

    GENERAl INfORMAtION Technical specifications Model Electrical characteristics Power supply 230/1/50 V/Ph/Hz Quantity Nominal power input 0,12 0,15 0,15 Nominal current consumption 0,52 0,70 0,70 Maximum air flow 1600 2050 2150 m³/h Medium air flow 1400 1900 1980 m³/h Minimum air flow 1280 1600 1800...
  • Page 7: Installation

    The document envelope must be kept in a safe place. Any duplicate must be requested from RIELLO S.p.A. which re- serves to charge the cost. Remove the supplied material and the control panel from...
  • Page 8: Storage

    INStAllAtION take into account the technical requirements, as well as any Model current local regulations. Product dimensions The product uses R32 refrigerant gas and must be installed in rooms with a minimum floor area, as indicated in the 1325 1650 1650 following table, depending on the total refrigerant charge of the system (given by the sum of the factory charge of the...
  • Page 9: Recommended Distances

    INStAllAtION ments, pipes or power lines HIGH SPACING DIStANCE Avoid: — installing the device in hallways or passageways — any obstacles or barriers that will cause the expelled air to recirculate — locations with aggressive or explosive atmospheres or with inflammable fluids —...
  • Page 10 INStAllAtION panels. WItHOUt fAlSE CEIlING Side panels removing: 10 ÷ 15 Fastening nut (supplied) Fastening nut M10 (not supplied) Ceiling WItH fAlSE CEIlING — open the fixing pin — open the air intake grill — unfasten the grid — repeat for all elements 10 ÷...
  • Page 11 INStAllAtION With false ceiling 10 ÷ 15 10 ÷ 15 Hole in false ceiling false ceiling Model — regulate the unit’s position so as to create a slope towards template dimensions the condensation drainage 1204 1530 — tighten the fastening nut Seal the nuts with some liquid thread lock.
  • Page 12: Refrigerating Connection

    INStAllAtION Drilling into the wall: Model Connections Liquid line 3/8” Inches connection Gas line 5/8” Inches connection Liquid line 9,52 5 - 6 mm connection Gas line 15,88 connection For indications concerning distances and differences in height of connection pipes, refer to the matching outdoor unit manual.
  • Page 13 INStAllAtION — remove burrs keeping the cut edge facing down Pipe Ø — remove the flare nut on the unit connection inches — insert it into the connection pipe 6,35 — flare the tube 9,52 12,70 15,88 — bring line ends with flare connection close to their cou- pling on the unit —...
  • Page 14: Condensate Discharge Connection

    INStAllAtION In case of use with outdoor temperature above 30 °C and relative humidity above 80%, increase wall thickness up to 20 mm. For gas pipes: — ensure that the material used resists to temperatures up >100mm to 120°C For liquid pipes: —...
  • Page 15 INStAllAtION Pre-cut metal sheet — select another connection — remove the pre-cut metal sheet — connect a circular duct to the prepared connection — seal the connection When removing the pre-cut sheet, take special care not to damage the internal components. The edges of the pre-cut sheet and its housing are sharp, use personal protection elements during the operations.
  • Page 16: Wiring Diagram

    INStAllAtION 2.12 Wiring diagram MODEl 100 - 125 - 140...
  • Page 17: Electrical Connection

    INStAllAtION 2.13 Electrical connection AMS P it leaves the factory completely wired, and only requires a connection to the outdoor unit. O F F Fixing screws Electric panel access panel Terminal blocks — position the system's main switch in the "OFF" position. To access the terminal board: —...
  • Page 18 INStAllAtION Model Electrical characteristics Power supply 230/1/50 V/Ph/Hz Power cable H07RN-F Type n. x Power cable 3 x 4 mm² n. x Signal cable 4 x 2,5 mm² The cable sections specified in the table are minimum re- quirements. The correct size must be calculated taking in- to account the actual length, the type of routing and other conditions set by the existing regulations.
  • Page 19: Remote Control

    INStAllAtION 2.14 Remote control DOOR ClOSED Control, setting and programming operations are carried out with the IR remote control. The electronics modulates the device operation according to the temperatures detected by the probes inside the indoor and out- door units. Battery insertion The remote control is powered by two AAA batteries (1.5 V) housed at the back, under a cover.
  • Page 20 INStAllAtION DOOR OPEN Switch on or off the unit display Indoor unit processing Press to restart the air conditioner Private function Keys locking Remote control display The remote control display shows the settings as changed by the user and the detected weather conditions. The backlit display is divided in areas according to function type.
  • Page 21: Unit Display

    INStAllAtION Unit display timer settings The unit display shows the active functioning mode, the tem- perature and the alarms, if any. Timer setting value or current time display Switch on timer enabled Switch off timer enabled functions Not available Sleep function enabled Fresh function enabled Not available for Consolle unit Display...
  • Page 22: Commissioning And Maintenance

    COMMISSIONING AND MAINtENANCE COMMISSIONING AND MAINtENANCE factory settings Preparation for first commissioning Description Prior to commissioning, it is necessary to check that: Model 35 — all the safety conditions have been met Model 50 — all distances have been respected Model 70 —...
  • Page 23: Putting Into Service

    COMMISSIONING AND MAINtENANCE — the current consumed by the compressor is less than the maximum permitted Indoor unit address — the device is operating under the recommended operating 0 (master) conditions 1 (slave) — the unit is able to stop and start up again 2 (slave) 3 (slave) Should any of the above-listed controls have problems: turn...
  • Page 24: Extraordinary Maintenance

    COMMISSIONING AND MAINtENANCE Monthly operations Proceed as follows to remove the capacitors: — carry out the evaporator emptying operation The following checks are part of the monthly maintenance plan: The operation is detailed in the Installer booklet of the — Cleaning the cabinet matching outdoor unit.
  • Page 25 COMMISSIONING AND MAINtENANCE Wi-Fi on Remote control receiver Temperature indication, alarm code Emergency switch Indoor unit faults LED1 Display Description Remarks Room probe fault Exchanger probe fault Microprocessor malfunction Communication error between indoor unit and outdoor unit The unit resets after problem Communication error between resolution unit and control panel...
  • Page 26: Disposal

    RECYClING AND DISPOSAl DISPOSAl Packaging materials shall be disposed of separately so as to re- cover and recycle them. At the end of its service life, the device shall be disposed of according to the existing legislation.
  • Page 27 RIELLO S.p.A. - 37045 Legnago (VR) tel. +39 0442 630111 - fax +39 0442 630371 www.riello.it As the manufacturer is constantly improving its products, the aesthetic or dimensional features, the technical data, the equipment and accessories indicated could be subject to variations.